19
Green Power 2.0
60-80 kVA - Ref.: IOMMASGPXX06-EN 06
ENGLISH
5. HUMAN MACHINE INTERFACE
5.2. MIMIC PANEL OVERVIEW
5.2-1
Status bar (always displayed)
UPS Rated Power (kVA)
Unit panel reference
Operating modes:
Normal
(Normal mode),
Eco
(Eco mode),
En. Saver
(Energy
Saver mode – parallel confi gurations only),
Standby
(Standby
program mode),
Service
.
Unit status:
• Displayed messages: ON MAINT. BYPASS, IMMINENT STOP,
ON BATTERY, BATTERY TEST, ON INVERTER, ON AUTO
BYPASS, UNIT AVAILABLE, UPS IN STANDBY, LOAD OFF.
-
Flashing red
: imminent UPS shutdown
-
Red
: Load not powered or battery circuit open
-
Flashing yellow
: UPS in standby mode or maintenance alarm
is active
-
Yellow
: UPS on battery or the UPS points out a particular
working mode
-
Flashing green
: battery test is in progress
-
Green
: the load is supplied
-
Grey
: inactive UPS
5.2-2
Alarms area
Alarms area
Present when an alarm is active.
Enter
ALARMS
menu to display the complete alarms list (see chapter 9).
5.2-3
Status icons
Key icon:
Displayed if the keypad has been locked.
Time:
UPS current time (hours and minutes, with ':' fl ashing).
USB icon:
Displayed if a USB memory stick is inserted.
It must be formatted with FAT32 fi lesystem.
Network icon:
Displayed if a valid link has been established on the ethernet.
Flashes when a remote host is communicating with the UPS.
Foreword: status icons and Time are only visible if there are no pending
alarms, as the alarm bar overwrites the icons when active.