2. INSTALLATION OF THE UNIT

2.5. ELECTRICAL 

REQUIREMENTS

The installation and system must comply with national plant regulations. 

The electrical distribution panel must have a protection and sectioning system installed for the input mains and auxiliary mains. 
Use a differential switch (type B) installed on the mains power switch, which must be inserted upstream from the distribution panel.

The table below shows the input protection devices recommended for the correct installation of an individual UPS.

The maximum cable sizes allowed are also included in the table.

Size of input protection devices

Model 

rating 

Magneto-

thermal Input

(1)

Magneto-

thermal Aux. 

Mains

(1)

Differential

input

(4)

Input/Output 

cable

core size

Aux cable 

core size

Battery cable 

core size

Battery 

protection

(3)

(kVA)

(A)

(A)

(A)

(mm

2

)

(mm

2

)

(mm

2

)

(A)

single

parallel

single

parallel

flexible 

cable

rigid

cable

flexible 

cable

rigid

cable

flexible 

cable

rigid

cable

max

(2)

max

(2)

max

(2)

max

(2)

max

(2)

max

(2)

60

125

160

125

160

0,5

50

70

95

95

95

95

200 aR

80

160

200

160

200

0,5

50

70

95

95

95

95

200 aR

(5)

(1)  Recommended magneto-thermal switch: four poles with intervention threshold curve C. It is necessary to use a D curve selective breaker if 

an optional external transformer is used.

(2) Determined by the size of the terminals.
(3) Protection on the external battery cabinet.
(4)  Caution! Use type B four-pole selective (S) circuit breakers. Load leakage currents are added to those generated by the UPS and during 

transitory phases (power failures and power returns) short current peaks may occur. If loads with high leakage current are present, adjust 
the differential protection. It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and 
operational with the definitive load, so as to prevent the sudden activation of the above switches.

(5) Use 250aR for a battery cabinet with capacity exceeding 90 Ah. 

The UPS is designed for transient overvoltages in category II installations. If the UPS is part of the building’s 
electrical circuit, or is likely to be subject to transient overvoltages in category III installations, additional external 
protection must be provided, either on the UPS or in the AC power supply network powering the UPS.

GENSET must support load variations from 0 to 100%.

WARNING!
As specified in 62040-3 Attachment 3: Non-linear Load Reference, in the event of three-phase non-linear loads 
connected downstream of the UPS, the neutral current on the load can be 1.5 - 2 times higher than the phase current. 
This must be considered when estimating the correct size of the output and the auxiliary neutral cables.

WARNING!
This is a product for commercial and industrial application in an industrial environment - installation restrictions or 
additional measures may be needed to prevent interference.

IMPORTANT!
Protective earthing conductor (PE) must have sufficient current-carrying capacity.
The PE cable core size must be chosen according to the PROTECTIVE CURRENT RATING of the earth circuit which 
depends on the provision and location of protective overcurrent devices. We suggest 35 mm

2

 for GP80 and 25 mm

2

 

for the Green Power 2.0 using the protective devices in the above table.

Содержание Green Power 2.0 60

Страница 1: ...d installation et d utilisation FI Manuel d installation et d utilisation FR Manuale di installazione e uso IT Installatie en bedieningshandleiding NL Dokumentacja Techniczno Ruchowa PL Manual de ins...

Страница 2: ...eriods of storage or UPS inactivity SOCOMEC may at its own discretion opt for the repair of the product or the replacement of faulty or defective parts with new parts or with used parts of equivalent...

Страница 3: ...GATION 22 6 OPERATING PROCEDURES 28 6 1 SWITCHING ON 28 6 2 COMMISSIONING WIZARD 28 6 3 SHUTDOWN 29 6 4 SWITCHING ONTO MAINTENANCE BYPASS 29 6 5 SWITCHING ON FROM MAINTENANCE BYPASS 29 6 6 EXTENDED OU...

Страница 4: ...f present between the said isolators and the UPS In particular the label must be attached to the external AC input line isolation service backfeed insulation Keep this manual in a convenient place for...

Страница 5: ...d warnings on labels and plates on the equipment should be complied with DANGER HIGH VOLTAGE BLACK YELLOW PROTECTIVE EARTH TERMINAL PE READ THE USER MANUAL BEFORE USING THE UNIT We advise you to conta...

Страница 6: ...ystems may be required to maintain these values Avoid dusty environments or areas where there is dust from conductive or corrosive materials e g metal dust or chemical solutions The UPS is not designe...

Страница 7: ...RS232 connector for modem E Cable run F Slots for optional cards G Fuse output socket for options H Fans I Fans J Power connections behind the plastic protection Q1 Input breaker MAINS SUPPLY Q3 Outp...

Страница 8: ...TALLATION OF THE UNIT 2 4 1 Electrical diagram 2 4 ELECTRICAL DIAGRAM The following is a simple electrical diagram of the UPS unit For connections details see chapter 3 PE BATTERY MAINS BKF AUX BKF UP...

Страница 9: ...y phases power failures and power returns short current peaks may occur If loads with high leakage current are present adjust the differential protection It is advisable in all cases to carry out a pr...

Страница 10: ...his manual and section 4 7 3 of standard CEI EN 62040 1 2009 05 The labels are supplied with the equipment Beware if there is a hazardous potential on neutral under certain irregular conditions or due...

Страница 11: ...d an early auxiliary contact as shown in figure 2 5 2 1 Electrical contact data 2 A 250 Vac Protection with Mains and Aux Mains connected separately Activating UPS protection access the MAIN MENU SETT...

Страница 12: ...nal block T1 Mains switch XB2 Not connected XB3 Mains BKF connector See also section 3 2 Remote switches rated current Model T1 T2 60 3 3 125 A AC1 125 A AC1 80 3 3 160 A AC1 160 A AC1 UPS BKF COMMON...

Страница 13: ...sed oors 3 1 Power connections A Power cables B Control cables Cable specifications strip length 18 mm tightening torque 3 5 4 5 Nm Protective Earth terminal PE see sec 2 5 A B B A 3 CONNECTIONS B2 CO...

Страница 14: ...AUX MAINS CONNECTED SEPARATELY 3 2 MAINS AND AUX MAINS CONNECTED TOGETHER B2 COM1 NC1 NC2 COM2 B1 B2 B1 L1 L11 L21 L31 L2 L3 N N1 L12 L22 L32 N2 B2 COM1 NC1 NC2 COM2 B1 B2 B1 L1 L11 L21 L31 L2 L3 N N1...

Страница 15: ...ge to the equipment Reassemble the plastic terminal block protection If using cabinets not supplied by SOCOMEC it is the installer s responsibility to check electrical compatibility and the presence o...

Страница 16: ...e auxiliary mains via automatic bypass Normal operation which is from the inverter returns automatically a few seconds after the overload disappears When the voltage generated by the inverter goes out...

Страница 17: ...d using the appropriate procedure the load is powered directly from the maintenance bypass while the UPS is separate from the power supply and can be switched off This operating mode can be selected f...

Страница 18: ...ypass procedures settings menu list of events and statistics 5 1 1 Display ESC button Exits current page aborts operations UP button Scrolls up through the available menus values UP DOWN button Scroll...

Страница 19: ...r maintenance alarm is active Yellow UPS on battery or the UPS points out a particular working mode Flashing green battery test is in progress Green the load is supplied Grey inactive UPS 5 2 2 Alarms...

Страница 20: ...Load level Green Yellow 5 2 4 Additional Icons On Maintenance Bypass Commissioning Code not inserted see chapter 5 3 9 or Scheduled Inspection warning machine inspection required call SOCOMEC support...

Страница 21: ...uous other levels ashing Battery discharging Bar colour yellow upper level ashing Battery charged Bar colour green Battery discharged Battery open Battery in alarm If there is a pending battery charge...

Страница 22: ...EN 06 5 HUMAN MACHINE INTERFACE 5 3 MENU NAVIGATION From the mimic panel page press the ENTER key to access the MAIN MENU Use the UP DOWN key to scroll menu items ENTER to confirm a choice ESC to exit...

Страница 23: ...23 Green Power 2 0 60 80 kVA Ref IOMMASGPXX06 EN 06 ENGLISH 5 HUMAN MACHINE INTERFACE 3...

Страница 24: ...an one page press UP DOWN to scroll pages 5 3 4 COMMANDS menu This menu contains the commands that can be sent to the UPS Some of them are password protected If a command is not available a COMMAND FA...

Страница 25: ...the situation over the last 14 days or in shorter periods last 24 hours last hour or last minute Enter the required menu and press UP DOWN to scroll through different periods The last page shows the...

Страница 26: ...available after restarting If the display doesn t restart automatically choose the RESTART DISPLAY command in COMMANDS menu To change the language go to the MAIN MENU PREFERENCES LANGUAGE Note to rest...

Страница 27: ...CES LANGUAGE DATE AND TIME BUZZER DISPLAY PASSWORDS REMOTE COMMANDS UPS SETTINGS OUTPUT BATTERIES TRANSFORMER BACKFEED CONNECTIVITY PERIPHERALS NETWORKS PARAMETERS NETWORK TCP PORTS MAIL ACCOUNT MODEM...

Страница 28: ...UPS PROCEDURES Select Automatic Start Procedure and press ENTER Carry out the operations indicated on the display In the case of UPSs connected in parallel choose the Automatic Start Procedure availa...

Страница 29: ...ment to be repaired Enter menu MAIN MENU COMMANDS UPS PROCEDURES Select ON MAINT BYPASS and press ENTER Carry out the operations indicated on the display If there is an external manual bypass carry ou...

Страница 30: ...onnected by means of Q3 If the UPS is operating from the maintenance bypass Q5 in position 1 with the mains present the emergency shutdown does not interrupt the power supply to the load In emergency...

Страница 31: ...ections can be made to satisfy the different levels of signalling and remote monitoring For UPS connected in parallel all options listed in this chapter must only be installed on the UPS in the parall...

Страница 32: ...he local network enter the MAIN MENU SETTINGS CONNECTIVITY PERIPHERALS NETWORK PARAMETERS menu disable the DHCP and save set the device network parameters according to those of the network and save 3...

Страница 33: ...You can click on the Input Battery Output Bypass symbols to access the relevant measurements Using the UPS MONITOR link on the menu it is possible to return to the UPS synoptic In the case of a paral...

Страница 34: ...ault 3 UPS Imminent Stop 4 UPS Overload 5 UPS On Battery 6 Battery Discharged 7 Temperature Alarm 8 Customer Input Alarm 9 UPS General Alarm The end of the event is notified by another e mail The mail...

Страница 35: ...l Alarm 2 OUT 2 ESD activation 1 OUT 3 Battery low or imminent stop 2 OUT 4 ESD activation 1 IN 1 1 ESD 1 IN 2 External alarm A39 2 IN 3 2 External alarm A40 2 7 3 ADC CARD To be installed in one of t...

Страница 36: ...OR This card s inputs outputs have the same functions as the ADC card with the exception of the third input IN3 CAUTION Two ADC cards with temperature sensor cannot be connected simultanously 7 5 ISOL...

Страница 37: ...rip coil TRIPPED TRIPPED POSITION for Q1 or Q4 when back feed alarm occurred To reset turn to OFF position then to restart switch to ON position 8 2 EXTERNAL MANUAL MAINTENANCE BYPASS The external man...

Страница 38: ...power supplied from an incorrectly sized GE A07 INSIDE OVER TEMPERATURE The UPS internal temperature is higher than 50 C please refer to the MEASUREMENTS menu on the HMI Check the ventilation or air c...

Страница 39: ...ce contract with the Remote Monitoring option is in place the procedure for analysing the UPS via remote connection will be automatically activated by your service centre provider A44 PERIODIC SERVICE...

Страница 40: ...conditions of use for analysis Since the expected lifetime of batteries is very much dependent on operating conditions number of charging and discharging cycles load rate temperature a regular inspec...

Страница 41: ...Pn 0 C 35 C kW 60 80 Overload 25 C Vin 380 Vbat 216 2 10 minutes 5 minutes 1 minute 30 seconds kW 67 5 75 81 90 90 100 108 120 Crest factor 25 C 2 7 Total harmonic output voltage distortion THDv 1 Ph...

Страница 42: ......

Страница 43: ...Green Power 2 0 P a r a l l e l C o n f i g u r a t i o n...

Страница 44: ...cables supplied allow a maximum distance of about 3 metres between the UPS units This gives enough room for an external battery cabinet to be inserted beside each UPS 11 3 POWER CONNECTIONS See chapt...

Страница 45: ...re has no battery cabinet Key A Auxiliary mains magneto thermal switch B Parallel bus cable C Single UPS magneto thermal auxiliary mains breaker D Single UPS magneto thermal input mains switch E 1 Out...

Страница 46: ...TIONS In order for units connected in a parallel configuration to operate correctly control cables are required to exchange data between the various UPS units making up the parallel system to manage c...

Страница 47: ...advantage of using ICM is that the options and the external communication accessories for system monitoring and diagnostics i e Net Vision ADC board etc can be installed only on one UPS In the UPS pa...

Страница 48: ...pact on the mains or GenSet when the UPS system resumes from battery mode The delay restart time from 0 to 65 seconds can only be set via ASSIST The delay restart rectifier T_delay_start_rect has to b...

Страница 49: ......

Страница 50: ......

Страница 51: ......

Страница 52: ...386 1 5807 860 Fax 386 1 561 11 73 info si socomec com SPAIN 836 3RZHU RQWURO QHUJ IILFLHQF Solar Tel 34 93 540 75 75 Fax 34 93 540 75 76 info es socomec com UNITED KINGDOM Power Control Energy Effici...

Отзывы: