2.5.2. Connecting the external backfeed protection
To ensure maximum protection, use a 220-240 V
release coil with integrated travel limit contact to pilot
the input protection systems (see section 2.5
“Electrical requirements”). If a trip coil without an
integrated end-of-travel contact is used, add an
early auxiliary contact as shown in figure 2.5.2-1.
Electrical contact data: 2 A 250 Vac
•
Protection with Mains and Aux Mains connected separately
Activating UPS protection: access the
MAIN MENU > SETTINGS > UPS SETTINGS > BACKFEED
and set the
BACKFEED TYPE
Parameter to
SEPARATE MAINS.