24
EN
ATyS d H - 544077E - SOCOMEC
Connections on the ATyS dH Terminals
Connections on the ATyS C55/C65 Terminals
A1-A2 : A Power Supply - Source I (230Vac Phase/ Neutral)
71 : Aux. Input – A Power Switch I is closed (ON)
B1-B2 : B Power Supply - Source II (230Vac Phase/ Neutral)
72 : Aux. Input – B Power Switch II is closed (ON)
CP – CN : Phase / Neutral internal dual power supply (DPS) output
73 : Aux. Input – A Power Switch I in position 0 (OFF)
AC1 – AC2 : Position I order input terminals
74 : Aux. Input – B Power Switch II in position 0 (OFF)
BC1 – BC2 : Position II order input terminals
70 : Common link for switch position aux. contacts
AT1 – AT2 : Position 0 order input terminals for switch I
11-21-31-41 : Common link for order Outputs
BT1 – BT2 : Position 0 order input terminals for switch II
14 : A Power Switch I closing (ON) order output
11-21-31-41 : Common link for switch positions aux. contacts outputs
24 : B Power Switch II closing (ON)order output
22 : Aux contact output - A Power Switch I in position 0 (OFF)
34 : A Power Switch I position 0 (OFF) order output
14 : Aux contact output – A Power Switch I is closed (ON)
44 : B Power Switch II position 0 (OFF) order output
34 : Aux contact output – B Power Switch II is closed (ON)
SOURCE 1 (L1-L2-L3-N) : 3 phase & N sensing power source A
42 : Aux contact output - B Power Switch II in position 0 (OFF)
SOURCE 2 (L1-L2-L3-N) : 3 phase & N sensing power source B