15
EN
ATyS d H - 544077E - SOCOMEC
5.6.
Assembly of customer mounted accessories
DANGER ! Never handle any customer mounted accessories while there may be the risk of voltage being
or becoming present.
Note: if you are using an external controller different from ATyS 55/65 please note that a delay timer in 0 position
(OFF-OFF) must be established with a minimum time of 1,5 seconds and the order signal from ATS controller to the
ATyS dH must be pulsed signals with pulse duration of at least 200ms. (Recommended pulse length : 300ms).
5.6.1.
ATS Controller for use with the ATyS d H
ATyS C55/C65 are ATS controllers. They ensure the automatic control of remotely operated transfer switching equipment
such as the ATyS r, ATyS S, ATyS d S, ATyS d M and ATyS d H as well as common contactors, circuit breakers or most
other motorised transfer switches.
ATyS C55 General characteristics
• Self-powered from sensing.
• Wide voltage range (88-576VAC).
• 24 VDC aux power supply (for optional use).
• 2 latching relays.
• Smart commissioning wizard.
• IP65 degree of protection with gasket (accessory).
• 1000 Alarms and Events.
• 6 fully configurable I/O.
• Genset scheduler.
• Door or back plate mounting.
• Main/Main, Main/Genset and Genset/Genset applications.
• Easyconfig configuration software.
• RS485 Modbus communication.
• Ethernet, SNMP, BACnet using DIRIS M-70 gateways. Includes
Webserver.
• A DIRIS Digiware D-70 gateway can be utilised as a remote
display for multiple ATyS C55 controllers; the D-70 also provides
Ethernet, SNMP & BACnet connectivity.
ATyS C65 General characteristics
• Self-powered from sensing.
• Wide voltage range (88 - 576 VAC).
• 24 VDC aux power supply (for optional use).
• 2 latching relays.
•
Digiware IO-10: I/O extension up to 30 inputs and 18 outputs.
• Power & Energy metering with /1 A or /5 A current
transformers.
• Energy backup.
• IP65 degree of protection (panel gasket included).
• 3000 Alarms and Events.
• Multiple fully configurable timers, thresholds and I/O.
• Easyconfig configuration software.
• Shock resistant IK08+.
•
Digiware compatible (replaces U module).
• Ethernet, SNMP, BACnet using DIRIS M-70 gateway. Includes
Webserver.
• A DIRIS Digiware D-70 gateway can be used as a remote display
for multiple ATyS C65 controllers; the D-70 also provides Ethernet,
SNMP & BACnet connectivity.