20
EN
ATyS d H - 544077E - SOCOMEC
5.6.6. ATyS C55/C65 controller wiring
Bottom view
Top view
TYPE
TERMINAL N°
DESCRIPTION
CHARACTERISTICS
RECOMENDED
CROSS SECTION
TIGHTENING
TORQUE
Sensing source 1
SOURCE 1
L1/L2/L3/N
Voltage sensing inputs source 1
& voltage supply (L1-L2)
Sensing voltage
50 - 575 V.a.c P-P - 50/60 Hz (+/- 10%)
Supply voltage (L1-L2)
88 - 576 V.a.c - 50/60Hz (+/- 10%) Ui 600V
0.75-2.5mm²
AWG 18-14
0.5-0.6 Nm
4.4-5.3 lb.in
Sensing source 2
SOURCE 2
L1/L2/L3/N
Voltage sensing inputs source 2
& voltage supply (L1-L2)
Inputs
71
IN1: programmable input 1
Do not connect to any external power
supply
0.5-2.5mm²
AWG 20-14
72
IN2: programmable input 2
73
IN3: programmable input 3
74
IN4: programmable input 4
75
IN5: programmable input 5
76
IN6: programmable input 6
70
Common point for inputs
Aux power supply
81/82
- : negative terminal for aux supply
+: positive terminal of aux supply
12-24 Vd.c.
Outputs
12/14/11
OUT1: programmable output 1
Dry contacts
8A / 277 VAC 50/60 Hz
5A / 24 VDC
1.5-2.5mm²
AWG 16-14
22/24/21
OUT2: programmable output 2
32/34/31
OUT3: programmable output 3
42/44/41
OUT4: programmable output 4
52/54/51
OUT5: programmable output 5 (latching)
62/64/61
OUT6: programmable output 6 (latching)
Current transformers
IN/I3/I2/I1
CT neutal / CT phase C / CT phase B / CT phase A
CT input 1A or 5A
Serial connection
RS485
Connection RS485
-: negative terminal of RS485 bus
+: positive terminal of RS485 bus
NC : Ground
RS485 bus insulated
LiYCY shielded twisted pair
0.14 to 1.5 mm²
30-14 AWG
0.22 -0.25 Nm
Digiware*
DIGIBUS
Connection point for I/O 10 optional accessories &
digiware connection (must use 24 VDC input)
RJ 45 digiware cable
-
-
* For more information check I/O module instruction sheet ref 545597