13
EN
ATyS d H - 544077E - SOCOMEC
5.2.
Mounting Orientation
4000 A
5000 A
6300 A
OK
Others positions are not allowed
CAUTION ! Always install the product on a flat and rigid surface paying attention to the net weight of the
product being installed.
5.3.
Control Wiring Connection Terminals 4000, 5000, 6300 A
‘A‘-Power Terminal Sensing
‘B‘-Power Terminal Sensing
‘A‘-Power Closing Terminal (ON)
‘B‘-Power Closing Terminal (ON)
‘A‘-Power Closing Terminal (OFF)
‘B‘-Power Closing Terminal (OFF)
‘A‘-Power Aux Switch
‘B‘-Power Aux Switch
‘A‘-Power Terminal Sensing
‘B‘-Power Terminal Sensing
‘A‘-Power Closing Terminal (ON)
‘B‘-Power Closing Terminal (ON)
‘A‘-Power Closing Terminal (OFF)
‘B‘-Power Closing Terminal (OFF)
‘A‘-Power Aux Switch
‘B‘-Power Aux Switch
Note: CP-CN output terminals are the dual power supply (DPS) phase/neutral control power output terminals
intended for use with position order signals. (Refer to chapter 5.6.7, page 21 for wiring with an ATyS C55/C65
ATS controller).
Note: on A1,A2,B1,B2 connections, a 6mm
2
cable and 65A peak protection devices must be used.