S N V 0 1 8 E C . X X
U S E R & I N S T A L L A T I O N M A N U A L
V 3 . 1
© SNV Engineering Ltd
3
Electrical
note
min
nom
max
Unit
Power supply
18
24
30
V dc
Consumption:
24V DC – 0A all 24 channels
24V DC – 13.5A all 24 channels
18V DC – 0A all 24 channels
18V DC – 13.5A all 24 channels
18V DC – 16A all 24 channels
Note 1,
2
Abs Max
21
45
29
68
30
54
39
79
86
mA
Measurement channel
resistance
each
12
mOhm
Channel maximum current
-16
16
A
Channel max working voltage
Note 3
1000
V dc
Current measurement range
Note 4
0.035
-
13.5
A
Note 1: The value is for each installed board
Note 2: The maximum number of cards to be installed in series is 127.
Note 3: Maximum working voltage 1000VDC for pollution degree 1. For pollution degree
2 the maximum working voltage is 800VDC.
Note 4: For software version > 2.1 values lower than 35mA are pulled down to zero
Physical & Environmental Characteristics
Details
Operating Temperature
-20 °C to +60 °C
Storage Temperature
-40 °C to +100 °C
Board Dimensions
08 channels: 165x100 mm
12 channels: 201x100 mm
16 channels: 237x100 mm
24 channels: 309x100 mm
See mechanical Specifications in ANNEX A
EMC – Emissions
Meets: EN 61326-1,
EN 61000-6-3, EN 50081-1, EN 55011
(Class B ITE: domestic environment)
EMC – Immunity
Meets: EN 61326-1, EN 50082-1,
EN61000-4-3 (Radiated EM fields immunity)
EN61000-4-4 (Fast transient burst (EFT))
EN61000-4-5 (Surges)
EN61000-4-6 (Conducted EM fields immunity)
Also successfully tested (Criterion A) at
Conducted immunity at 10Vrms, and Radiated
immunity at 10V/m (instead of 3Vrms and 3V/m
required from the above standards)
Safety
Meets EN 61010-1
Measurement Category
RATED CLASS I and RATED TRANSIENT
OVERVOLTAGES 1,5KV
Usage
Indoor or outdoor use installed
in a metallic and/or plastic box
Содержание SNV018EC.XX
Страница 37: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 34 ...
Страница 38: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 35 ...
Страница 39: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 36 ...
Страница 40: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 37 ...
Страница 41: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 38 ...