S N V 0 1 8 E C . X X
U S E R & I N S T A L L A T I O N M A N U A L
V 3 . 1
© SNV Engineering Ltd
29
SNV012EC.B - MODBUS Function (17)
Function
SubFunction
Data Length
Values
Description
17 (0x11)
Report Slave ID (Serial Line only)
Response:
0x11
BQ
1 Byte
0x00 - 0xFF
Byte Count
SID
1 Byte
0x00 - 0xFF
Slave ID
IS
1 Byte
0x00 or 0xFF
Run Indicator Status
AD
Additional Data
Error Report:
0x91
2 Byte
Error
x01
-
Function unsupported
x04
-
Erron in reading register
according to MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b - paragraph 6.13
SNV012EC.B - MODBUS Function (20)
Function
SubFunction Data
Length
Values
Description
20 (0x14)
Read File Record
BQ
1 Byte
0x07 - 0xF5
Byte Count
RT
1 Byte
0x06
Sub-Req. x, Reference Type
FN
2 Byte
0x0001 - 0xFFFF
Sub-Req. x, File Number
RN
2 Byte
0x0001 - 0x270F
Sub-Req. x, Record Number
RL
=N
0x0000 - 0xFFFF
Sub-Req. x, Record Length
...
Sub-Req. x+1, ...
Response:
0x14
RDL
1 Byte
0x07 - 0xF5
Resp. data Length
RFL
1 Byte
0x07 - 0xF5
Sub-Req. x, File Resp. length
RRT
1 Byte
0x06
Sub-Req. x, Reference Type
RRD N x 2 byte
Sub-Req. x, Record Data
...
Sub-Req. x+1, ...
Error Report:
0x94
2 Byte
Error
x01
-
Function unsupported
x02
-
Address error
x03
-
Error in register quantity (1-125)
x04
-
Erron in reading register
x08
-
according to MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b - paragraph 6.14
Содержание SNV018EC.XX
Страница 37: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 34 ...
Страница 38: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 35 ...
Страница 39: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 36 ...
Страница 40: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 37 ...
Страница 41: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 38 ...