S N V 0 1 8 E C . X X
U S E R & I N S T A L L A T I O N M A N U A L
V 3 . 1
© SNV Engineering Ltd
27
Response:
0x01
-
2 Byte+N(2 Byte)
BCN
1 Byte
=N
Byte count
RG_H
1 Byte
N byte
Coil Status
N times Hi and Lo for N Coils
Error Report:
0x81
2 Byte
Error
x01
-
Function unsupported
x02
-
Address error
x03
-
Error in register quantity (1-125)
x04
-
Erron in reading register
according to MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b - paragraph 6.1
SNV012EC.B - MODBUS Function (4)
Function SubFunction
Data
Length
Values
Description
4 (0x04)
-
Read Input Registers
SA_H
1 Byte
0x00 -
0xFF
Starting Address Hi
SA_L
1 Byte
0x00 -
0xFF
Starting Address Lo
QI_H
1 Byte
0x00 -
0x00
Quantity of Input
Registers Hi
QI_L
1 Byte
0x01 -
0x7D
Quantity of Input
Registers Lo
Response:
0x04
-
2 Byte+N(2 Byte)
BCN
1 Byte
=2xN
Byte count
RG_H
1 Byte
0x00 -
0xFF
Register value Hi
RG_L
1 Byte
0x00 -
0xFF
Register value Lo
N times
Hi and
Lo for N
Registers
Error Report:
0x84
2 Byte
Error
x01
-
Function unsupported
x02
-
Address error
x03
-
Error in register
quantity (1-125)
x04
-
Error in reading
register
according to MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b - paragraph 6.4
Содержание SNV018EC.XX
Страница 37: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 34 ...
Страница 38: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 35 ...
Страница 39: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 36 ...
Страница 40: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 37 ...
Страница 41: ...S N V 0 1 8 E C X X U S E R I N S T A L L A T I O N M A N U A L V 3 1 SNV Engineering Ltd 38 ...