S N V 0 1 8 E C . X X
U S E R & I N S T A L L A T I O N M A N U A L
V 3 . 1
© SNV Engineering Ltd
26
holding registers (MODBUS function 16)
Address
Type
Description
dec
hex
0
0x 00
Hi byte
Commands: “hold”(0x01) or “mark”(0x02) or
“change address”(0x0A)
Lo byte
if command is “change address”,
then set new target address
1
0x 01
Hi byte
if command is “change address”,
then set new target address
Lo byte
if command is “change address”,
then set new target address
Modbus package structure:
Implemented Modbus functions are described in the following tables.
CAUTION
Do not use functions 20 and 21.
SNV012EC.B - MODBUS Function (1)
Function SubFunction
Data
Length
Values
Description
1 (0x01)
-
Read Coils
SA_H
1 Byte
0x00 - 0xFF Starting Address Hi
SA_L
1 Byte
0x00 - 0xFF Starting Address Lo
QI_H
1 Byte
0x00 - 0x00 Quantity of Input Registers Hi
QI_L
1 Byte
0x00 - 0xFF Quantity of Input Registers Lo
Quantity: 1 to 2000 (0x07D0)