Power supply ICOS-PS 3160 series
Installation, use and maintenance manual - EN
Ver. 1.05
40
CAUTION
ATTENTION
The reactor must be adequately sized, in order to:
• can withstand the current RMS value without overheating;
• doesn't saturate when the current reaches its peak value (pls. see graphs).
• can withstand continuously the working voltage without interruptions; for the purpose of selection, suppose
overvoltage category III.
The maximum length of the conductors used to wire the reactor must be less than 3 meters; they should be
kept as far away as possible from signal carrying conductors in order to avoid interferences.
Large capacitors inside the device. Risk of Electric Shock; wait at least No. 600 seconds (10
minutes) after disconnecting power. Do not connect or disconnect cable and connectors be-
fore that time.
Hautes capacités présentes à l'intérieur de l'appareil. Risque de choc électrique; attendez
au moins 600 secondes (10 minutes) après la mise hors tension. Les câbles et les connec-
teurs ne doivent pas être connectés ou déconnectés avant la fin du temps indiqué.
If the reactor is not used, put a jumper on connector J4, by using a 6 mm
2
/ 8 AWG wire.