Power supply ICOS-PS 3160 series
Installation, use and maintenance manual - EN
Ver. 1.05
23
CAUTION
ATTENTION
The following paragraphs describe in detail how to make connections.
For safety reasons, the device must always operate with the PE (Ground) terminal connect-
ed, to avoid electrical shock. The PE (Ground) connection must be carried out by means of
the specific terminal; do not rely on the mechanical fastening screws only.
The PE (Ground) protective conductor section must not be lower than 2.5 mm
2
/ 12 AWG,
according to IEC 61800-5-1 standard. Should the conductor be without mechanical protec-
tion, the section must be increased to 4 mm
2
/ 10 AWG.
Pour des raisons de sécurité, l'appareil doit toujours fonctionner avec la connexion PE
(Ground) insérée. risque d'électrocution! Le raccordement de PE (Ground) doit être effectué
à l'aide de la vis appropriée, en évitant de compter uniquement sur les vis de fixation méca-
niques.
La section du conducteur de protection PE (Ground), conformément à la norme CEI 61800-
5-1, ne doit pas être inférieure à 2,5 mm2 / 12 AWG. Si ce conducteur ne dispose pas de
protection mécanique, cette section doit avoir une taille minimale de 4 mm2 / 10 AWG.