Basic Operation 

The SMCSD10-Z is equipped with an intuitive 
normal mode.  

Normal Mode 

 

In normal operating mode, the Status LED 
flashes once every 8 seconds. 

 

In alarm mode, the red Status LED is ON. 

 

In trouble or maintenance mode, the Status 
LED is OFF. 

 

In battery replacement mode, the SMCSD10-Z 
turns OFF the Status LED and chirps every 45 
seconds until the batteries are replaced. 

Note:

 

You can view modes from the Touchscreen. 

Testing the SMCSD10-Z 

This section provides general guidelines for 
testing the SMCSD10-Z with the Touchscreen. For 
detailed instructions on how to put your 
Touchscreen into test mode refer to the 
Touchscreen documentation.  

Using Test Button 

A.

 

Press the SMCSD10-Z 

Test

 button for 10-to-15 

seconds. The SMCSD10-Z sends a signal to the 
Touchscreen. 

B.

 

At the Touchscreen, verify the signal was 
received. A message will appear in the upper 
right corner of the Touchscreen for 5 
seconds. 
 

Using Alarm Test Mode  

A.

 

Be sure the SMCSD10-Z is operating normally. 

B.

 

Set the Touchscreen to sensor test mode to 
prevent an alarm signal from being sent to 
the central-monitoring station if you have a 
monitored system. 
- From the Home screen, touch the Settings 

widget.  

-At the keypad, enter the Customer’s master 

keypad code  

-At the Settings Menu, touch 

Security > 

Alarm Tests

 

-Follow the Touchscreen’s provided 

directions to place it into Test Mode.  

C.

 

To generate a test alarm, press and hold 

Test

 Button for 15 seconds. An alarm 

message is sent to the Touchscreen. The 
Touchscreen alarm will sound as each sensor 
is tested.  

D.

 

Once completed, exit Test Mode from the 
Touchscreen. 

Using Smoke 

The SMCSD10-Z can be tested during install or at 
any time. It is recommended the SMCSD10-Z be 
tested in place annually. 

A.

 

Use 

Smoke! in a Can

® and follow the 

directions on the can. 

B.

 

Hold a smoldering punk or cotton wick close 
to the SMCSD10-Z and gently direct the 

smoke into the smoke entry openings for 20 
seconds or until an alarm is indicated. 

C.

 

The LED should stay ON and an alarm should 
be indicated at the Touchscreen. Extinguish 
the smoke source after testing. 

Wireless Signal Strength Test 

Note:

 

This step should only be performed by a 

qualified service technician. 

A.

 

From the Home screen, touch the Settings 
widget.  

B.

 

At the keypad, enter the Installer’s keypad 
code (not the customer’s Master keypad 
code).  

C.

 

At the keyboard screen, enter your 
Technician Code and touch 

Done

D.

 

At the Installer Settings Menu, touch 

Sensors 

& Zones > Sensor Diagnostics

 

E.

 

At the next screen, choose the security zone 
containing the smoke detector.  

F.

 

At the Sensor Diagnostic screen, verify the RF 
signal strength and other parameters. 
 

9   

Defaulting the Detector 

This step should only be performed by a qualified 
service technician. 

A.

 

Remove the SMCSD10-Z from the mounting 
plate. 

B.

 

Remove the two batteries. 

Содержание SMCSD10-Z

Страница 1: ...Pre installation Considerations Install the SMCSD10 Z in accordance with the National Fire Protection Association s NFPA Standard 72 Chapters 2 and 8 Depending on the application you may need to reference other chapters of NFPA 72 or NFPA 101 Choosing an Installation Location When choosing an installation location consider Use of structure and type of construction Contents you want to protect and ...

Страница 2: ...t smoke from reaching a smoke detector Within 10 feet 3 m of fluorescent light fixtures Not suitable for outdoor use WARNING LIMITATIONS OF SMOKE DECTECTORS The SMCSD10 Z Smoke Detector does not contain a built in audio alarm It is not intended for stand alone use it MUST be used with an approved Touchscreen Wireless smoke detectors are very reliable but may not work under all conditions No fire a...

Страница 3: ...atteries Do not replace with batteries that were used previously D Reattach the SMCSD10 Z to the mounting base and test the system E The SMCSD10 Z ships with a dust cover for protection on construction sites with dusty environments If your product is new remove the red plastic dust cover from the SMCSD10 Z 6 Pairing with Touchscreen Each SMCSD10 Z is programmed with a unique ID when manufactured T...

Страница 4: ...SMCSD10 Z Add the SMCSD10 Z to the Touchscreen before physically mounting it in the desired location A Test communications between the Touchscreen and the SMCSD10 Z as follows before permanently mounting the SMCSD10 Z Hold the SMCSD10 Z where you plan to install it Press the SMCSD10 Z Test button for 10 to 15 seconds The SMCSD10 Z sends a signal to the Touchscreen At the Touchscreen verify the sig...

Страница 5: ...e At the Settings Menu touch Security Alarm Tests Follow the Touchscreen s provided directions to place it into Test Mode C To generate a test alarm press and hold Test Button for 15 seconds An alarm message is sent to the Touchscreen The Touchscreen alarm will sound as each sensor is tested D Once completed exit Test Mode from the Touchscreen Using Smoke The SMCSD10 Z can be tested during install...

Страница 6: ...ng Zone Event History on this page To bypass a zone A With the system disarmed tap the Security app on the Home screen B Tap the Turn Zone Off button for the smoke detector The Turn Zone Off button changes to Turn Zone On C When the system is disarmed the Security Status header shows that some zones have been bypassed 12 Deleting a Sensor Deleting a sensor from the premises removes it as a monitor...

Страница 7: ...F until the SMCSD10 Z is serviced To place the SMCSD10 Z in diagnostic mode A Press the Test Button on the smoke detector for 5 seconds When the test starts the smoke detector LED flashes 1 to 9 times B Count the LED flashes and see the table below to determine the status of the smoke detector sensitivity and any action to take Flash Meaning Steps to Take 1 Unserviceable hardware fault Reset unit ...

Страница 8: ... Replace the batteries using the directions in section 5 of this guide 14 Troubleshooting The SMCSD10 Z does not power up properly or reports low battery Be sure the batteries are fully seated within the battery compartment and the polarity is correct Check the battery voltage 3 0 VDC nominal Touchscreen does not respond Follow the instructions in section 9 of this guide to test the SMCSD10 Z link...

Страница 9: ... Battery Life 5 years typically USensor Photoelectric Sensitivity 2 2 1 3 ft Drift Compensation Adj 0 5 ft max Heat Detection Fixed 135 F 5 F 57 2 C 2 8 C Heat Rate of Rise 15 F min 105 F 8 3 C min 40 6 C Low Battery Beep 1 every 45 seconds RF Wireless Frequency 2 4 GHz Weight w battery 0 20 lbs 0 09 kg Dimensions 5 6 x 2 4 14 2cm x 6 1cm Storage temperature 4 to 140 F 20 to 60 C Operating environ...

Страница 10: ...codes and standards or by the authority having jurisdiction NFPA 72 8 1 4 1 3 2 Detection in New Apartment Buildings Approved single station smoke alarms shall be installed in accordance with 7 6 2 10 of NFPA 101 outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the dwelling unit including basements 101 18 3 4 4 2 For exceptions refer to this section of NFP...

Страница 11: ...ediately Don t stop to pack or search for valuables In heavy smoke hold your breath and stay low crawl if necessary The clearest air is usually near the floor If you have to go through a closed door carefully feel the door and door knob to see if undue heat is present If they seem cool brace your foot against the bottom of the door with your hip against the door and one hand against the top edge O...

Отзывы: