5.9 Offset function
5.9.1
Offset function
This is a function that controls the "circulating fluid display temperature" and
the "target temperature for chiller temperature control" by shifting the
temperature for the set offset value.
This product has three different modes of offset functions (MODE 1 to 3).
(The default setting of this function is “OFF”.)
See "Table 5.9-1
Offset function" shown below for these modes.
Refer to "5.9.2 Usage example of offset function" for operation methods.
Refer to "5.9.3 Setting/checking of offset function" for the setting
instructions.
[When communication is being used]
The circulating fluid temperature sent by serial communication is the
circulating fluid temperature (the circulating fluid temperature after offset)
which is displayed on the thermo-chiller.
Table 5.9-1
Offset function
Offset function
Circulating fluid display
temperature
Temperature control
MODE1
Displays the "circulating fluid
discharge temperature".
Circulating fluid temperature is
controlled
to
be
"the
set
circulating fluid temperature plus
offset temperature".
MODE2
Displays the temperature that is
"circulating
fluid
discharge
temperature
plus
offset
temperature".
Circulating fluid temperature is
controlled
to
be
"the
set
circulating fluid temperature".
MODE3
Displays the temperature that is
"circulating
fluid
discharge
temperature
minus
offset
temperature".
Circulating fluid temperature is
controlled
to
be
"the
set
circulating fluid temperature plus
offset temperature".
OFF
(Default)
Displays the "circulating fluid
discharge temperature".
Circulating fluid temperature is
controlled
to
be
"the
set
circulating fluid temperature".
Содержание HRS090-A...-20 Series
Страница 8: ...HRX OM T002 Contents HRS090 Series...
Страница 20: ...HRX OM T002 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS090 Series 2 6...
Страница 64: ...HRX OM T002 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRS090 Series 4 10...
Страница 188: ...HRX OM T002 Chapter 9 Documents 9 9 Daily Check Sheet HRS090 Series 9 16...
Страница 191: ......