HRX-OM- T002 

Chapter  9      Documents 

 

HRS090 Series 

9.6 Types of hazard labels 

 
 

9-11 

 

9.6  Types of hazard labels   

(For HRS090-



-40-

The product has various potential hazards and they are marked with 
warning labels. Be sure to read this section before starting any work on the 
product. 

 

  Warning related to electricity 

 

 

Warning related to high temperatures 

 

 

 

Warning related to rotating objects (Air cooled type only) 

 

 

This symbol stands for a possible risk of cutting fingers or hand, or 
entanglement by rotating fan (For air-cooled type). 
The product contains a cooling fan that rotates during operation of the 
product.

The fan can start and stop intermittently and without warning.   

 

DO NOT operate the product without cover panels fitted.   

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

This symbol stands for a possible risk of hot surface and burns. 
 
The product has surfaces that can reach high temperatures during 
operation. Even after the power is turned off, there can still be residual 
heat in the product. 

 

DO NOT operate the product without cover panels fitted.   

 

DO NOT start working inside the product until the temperature has   
decreased sufficiently.   

This symbol stands for a possible risk of electric shock. 
 
The product is operated at high voltage and contains uncovered live 
terminals inside. 
DO NOT operate the product without cover panels fitted. 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 
DO NOT work inside this product unless you have been trained to do 

so. 

 

Содержание HRS090-A...-20 Series

Страница 1: ...ition Jul 2014Rev B Nov 2016 Operation Manual Installation Operation Original Instructions Thermo chiller HRS090 A 20 HRS090 A 40 HRS090 W 20 HRS090 W 40 Keep this manual available whenever necessary...

Страница 2: ...ion and operation of the product Only people who understand the basic operation of the product through this manual or who perform installation and operation of or have basic knowledge about industrial...

Страница 3: ...and Function of Parts 2 2 2 2 1 HRS090 A 20 In case of air cooled type 2 2 2 2 2 HRS090 W 20 In case of water cooled type 2 3 2 3 Function of Parts 2 4 2 4 Operation display panel 2 5 Chapter 3 Trans...

Страница 4: ...Display and setting of various functions 5 1 5 1 List of function 5 1 5 2 Function 5 2 5 2 1 Key operations 5 2 5 2 2 List of parameters 5 4 5 3 Main Display 5 7 5 3 1 Main Display 5 7 5 3 2 Items on...

Страница 5: ...pressure unit change 5 34 5 15 Data reset function 5 35 5 15 1 Data reset function 5 35 5 15 2 How to operate reset function 5 35 5 16 Accumulated Operating Time Reset Function 5 36 5 16 1 Accumulated...

Страница 6: ...aily check 8 2 8 2 2 Monthly check 8 3 8 2 3 Inspection every 3 months 8 4 8 2 4 Inspection every 6 months 8 6 8 2 5 Inspection during winter season 8 7 8 3 Consumables 8 7 8 4 Operation Stop for an E...

Страница 7: ...HRS090 Series 9 5 1 HRS090 A W 20 40 9 10 9 6 Types of hazard labels 9 11 9 6 1 Locations of Hazard Labels 9 12 9 7 Compliance standard 9 13 9 8 Sample DoC 9 14 9 9 Daily Check Sheet 9 15 Chapter 10 P...

Страница 8: ...HRX OM T002 Contents HRS090 Series...

Страница 9: ...ty related information in this manual carefully before starting work The safety manager is responsible for strictly observing safety standards but responsibility in respect to safety standards during...

Страница 10: ...ing to severity DANGER WARNING CAUTION 1 3 2 Definition of Serious injury and Minor injury Serious injury This term describes injuries that result in after effects including loss of eyesight burns ele...

Страница 11: ...is needed when contacting an SMC sales distributor How to see the serial number T O 001 January 2014 S O 001 Year Symbol Remarks Month Symbol Remarks Serial no 2015 T Repeated from A to Z in alphabeti...

Страница 12: ...en or sick condition which might cause an accident Do not remove the panels except for the cases permitted in this manual Do not remove the panels during operation Do not handle this product by any me...

Страница 13: ...of the product must be handled by a specialized industrial waste disposal agency in accordance with local laws and regulations Only maintenance personnel or qualified people are allowed to open the c...

Страница 14: ...Safety Data Sheet MSDS HRS090 Series 1 6 1 8 Material Safety Data Sheet MSDS If the material safety data sheets of chemicals used in this product are needed contact an SMC s sales distributor Any che...

Страница 15: ...4 Product Label and check the part number of the product HRS090 Cooling capacity Cooling method Piping thread type Power supply Options A Air cooled refrigeration None Nill Nill Rc F G Rc G thread ad...

Страница 16: ...ble 2 1 Accessory list Alarm code list label 2pcs English 1pc Japanese 1pc Operation manual 2pcs English 1pc Japanese 1pc Y strainer 40 meshes 25A 1pc Barrel nipple 25A 1pc Anchor brackets The anchor...

Страница 17: ...st Alarm code list label 2pcs English 1pc Japanese 1pc Operation manual 2 Copies English 1 copy Japanese 1 copy Y strainer 40 meshes 25A 1pc Barrel nipple 25A 1pc Anchor brackets The anchor bolts are...

Страница 18: ...filter periodically For details prefer to 8 2 2Monthly check Power cable entry Insert the power cable to the power cable entry and connect it to the power terminal For details refer to 3 3 2Electrica...

Страница 19: ...3 seconds Blinks during warming up function During standby Turns ON for 0 5 seconds and OFF for 3 seconds During operation Interval 0 3 seconds 4 4 ALARM light Blinks with buzzer when alarm occurs In...

Страница 20: ...HRX OM T002 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS090 Series 2 6...

Страница 21: ...have the licenses Be sure to use all the four eye bolts when sling the product The slant angle of each rope should be 60 degrees oe less When the product is carried by using folklift make sure that t...

Страница 22: ...ting and hanging position This drawing is HRS090 A 20 Table 3 1 Weight of the product Model Weight kg HRS090 A 20 40 Approx 136 HRS090 W 20 40 Approx 124 The product are heavy object Refer to Table 3...

Страница 23: ...is a heavy object Refer to Table 3 1 Weight of the product Moving the product by casters should be done by 2 persons or more Raise the adjuster feet and push the corners of the product when moving th...

Страница 24: ...ocation that is near heat sources and poor in ventilation Location that is subjected to abrupt changes in temperature Location that is subjected to strong electromagnetic noise intense electric field...

Страница 25: ...es in the product will be lower in the location at altitude of 1000m or higher For this reason the maximum ambient temperature for the thermo chiller operation and the cooling capacity will be reduced...

Страница 26: ...itioned ventilate by installing a duct on the outlet ventilation of the product Do not fasten the duct on the outlet ventilation of the product directly Have the space at least the dust s diameter apa...

Страница 27: ...40 Approx 17 Refer to 9 1 Specifications Installation environment specification Sound noise HRS090 A 73dB A HRS090 A 40 75 dB A HRS090 W 65dB A Front 1m height 1m rated condition The water cooled prod...

Страница 28: ...Space It is recommended to keep the space around the product shown in Fig 3 3 Fig 3 3 Installation space This drawing is HRS090 A 20 Have an enough space for the ventilation for the product Otherwise...

Страница 29: ...in Fig 3 4 Installation procedures This drawing is HRS090 A 20 Install the product on the horizontal floor Prepare the M10 anchor bolts that are appropriate to the material of the floor that the produ...

Страница 30: ...ttom of the product to fix the product to the floor using anchor bolts Fig 3 5 Fixtures and holding screws This drawing is HRS090 A 20 1 Install anchor bolts on the levelled floor with dimensions belo...

Страница 31: ...o the anchor bolts and screw the holding screws into the product to settle the product to the floor Fixture is mounted to the front and the rear surface of the product 2 places Tips SMC Foundations bo...

Страница 32: ...ce of cables being applied to the terminals Incomplete wiring or improper securing of wiring may cause electrical shock excessive heat and fire Ensure a stable power supply with no voltage surges Ensu...

Страница 33: ...2 Earth leakage breaker 1 Rated current A Sensitivity of leak current mA HRS090 A 20 HRS090 W 20 200 200 230VAC 50 60Hz 3phase M5 R5 5 5 4 cores x AWG10 4 cores x 5 5mm2 including ground 30 30 HRS090...

Страница 34: ...has knowledge and experience Check the power supply Operation with voltages capacities and frequencies other than the specified values can cause fire and electrical shock Wire with an applicable cable...

Страница 35: ...er operating time as than this for the user s side primary side If it is a shorter operating time there is a possibility of accidental breaker trip due to the internal motors inrush currents of this p...

Страница 36: ...1 Remove 4 screws to remove the power supply terminal cover on the back of the product Fig 3 8 Removal of power supply terminal cover 2 Hold the pull of the power supply terminal cover Pull the bottom...

Страница 37: ...wer supply terminal cover grommet with film Fig 3 10 Cable entry 4 Connect the power supply and the ground cable as shown in the figure below Fig 3 11 Wiring of power supply cable Power supply cable e...

Страница 38: ...HRX OM T002 Chapter 3 Transport and Setting Up 3 3 Installation HRS090 Series 3 18 Mount the power supply terminal cover using 4 screws Fig 3 12 Mounting of power supply terminal cover Screw...

Страница 39: ...3 3 7 Wiring of contact output signal Use the signal cable described below for wiring of each function Signal cable Use the cable and terminals as follows below for wiring of each function Table 3 5...

Страница 40: ...5 6 7 24VDC DC 24V 10 500mA MAX 1 13 14 15 24V COM Contact input signal 1 3 Contact input signal 1 Run stop signal input External switch signal input 2 Switch the input on the operation display panel...

Страница 41: ...This wiring is an example Fig 3 13 Wiring of Run stop signal input Remote signal input Example Terminal No 5 Terminal No 13 T e inal No 3 Terminal No 11 Switch Terminal No 3 Signal cable entry Note Ho...

Страница 42: ...ernal switch cannot be connected to the contact input signal 1 depending on the communication mode Table3 9 External switches used in the examples Table 3 8 Sets external switch Communication mode 1 C...

Страница 43: ...e flow switch described in the table purchasing separately 2 Depending on the external switch output type connect the wire the switch to the terminals for contact input signal as shown below This is a...

Страница 44: ...Category Communication mode LOC LOC 5 20 Communication setting menu Contact input output communication Contact input signal 1 RUN SW_A Contact input signal 1 type ALT ALT Contact input signal 1 delay...

Страница 45: ...f Contact open Contact output signal 3 Terminal no 2 10 Alarm status signal output B While alarm being generated Contact open While alarm not being generated Contact closed With power supply shut off...

Страница 46: ...ow for connecting multiple thermo chillers Configuration of connection One thermo chiller for one host computer or multiple thermo chillers for one host computer 31 thermo chillers can be connected at...

Страница 47: ...of alarm condition can be performed by remote control Refer to the Communications Operation Manual for more details Wiring of communication cable Be sure to wire as shown in the figure below Configura...

Страница 48: ...the piping may be damaged Facility water temperature of the facility water outlet port might rise up to approx 60deg C 3 4 Piping Piping port size Table 3 12 Piping port size Name Port size 1 Recomme...

Страница 49: ...Without holding the ball valve of the drain port with a wrench the ball valve may rotate and it may cause a fluid leakage and or malfunction of the product Be sure to hold the ball valve of the drain...

Страница 50: ...erflow port For option J Drain port To sump pit Customer s system 2 2 2 1 2 4 3 5 1 1 1 7 6 6 9 8 Water supply Fig 3 20 Recommended piping circuit No Name Size 1 Valve Rc1 2 2 Valve Rc1 3 Y strainer 2...

Страница 51: ...t causes the alarm AL01 Low level in tank When the circulating fluid temperature is lower than 10 deg C use 15 aqueous solution of ethylene glycol Otherwise it may cause icing of the fluid Tank lid Ci...

Страница 52: ...olution separately To control the density of the ethylene glycol aqueous solution a densitometer is available sold separately from SMC Item No Remarks Ethylene glycol aqueous solution 60 HRZ BR001 Ple...

Страница 53: ...ize Piping specifications Automatic water fill inlet Rc3 8 Supply pressure 0 2 to 0 5MPa Supply temperature 5 to 40 Overflow outlet Rc3 4 Piping should be within f19 of I D and 5m of length Riser pipi...

Страница 54: ...HRX OM T002 Chapter 3 Transport and Setting Up 3 6 Option J Piping of Automatic fluid filling HRS090 Series 3 34...

Страница 55: ...nfirm that the fluid level is between HIGH and LOW levels of the fluid level gauge Facility water piping For water cooled type Check that the piping is correctly connected to the facility water inlet...

Страница 56: ...e operation display panel Then the display moves to the main display which shows the circulating fluid outlet temperature The set circulating fluid temperature is displayed as SV on the digital displa...

Страница 57: ...4 2 3 Setting of circulating fluid temperature Press the or button on the operation panel to change the SV to the required value When setting the circulating fluid temperature by communication refer...

Страница 58: ...tton simultaneously The pump operates independently while the PUMP button is being pressed The RUN light green blinks while the pump is operating independently and the circulating fluid in the tank is...

Страница 59: ...up to the H mark on the tank Fig 4 6 Filling of Circulating Fluid Reset alarms on the Alarm menu screen Alarm reset is not accepted from any screen except the Alarm menu screen Refer to 5 2 1 Key oper...

Страница 60: ...luid temp Circulating fluid set temp Press the PUMP button press the RUN STOP button and the MENU button simultaneously again to operate the pump individually Fig 4 7 Alarm release 5 Repeat steps 1 to...

Страница 61: ...RUN STOP key on the operation panel he RUN LED green turns ON and the product starts running The circulating fluid discharge temperature PV is controlled to the set temperature SV Fig 4 8 Starting the...

Страница 62: ...use a failure 4 4 2 Stopping the product 1 Press the RUN STOP button on the operation panel The RUN light on the operation panel blinks green at 1 second intervals and continues operation to prepare t...

Страница 63: ...the specification range 4 6 Adjustment of Circulating Fluid flow rate When the circulating fluid flow rate is smaller than the minimum required the product may fail to maintain the performance making...

Страница 64: ...HRX OM T002 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRS090 Series 4 10...

Страница 65: ...erature offset between the discharge temperature of the thermo chiller and the customer s device 5 9 8 Reset after power failure Start operation automatically after the power supply is turned on 5 10...

Страница 66: ...e READY band width READY time Offset mode Offset temperature Recovery from power failure Anti freezing function Data reset Pump accumulated operating time reset Fan accumulated operating time reset Co...

Страница 67: ...ut signal 1 Contact input signal 1 type Contact input signal 2 Contact input signal 2 type Contact output signal 1 function Contact output signal 1 operation Contact output signal 1 selected alarm Dig...

Страница 68: ...t Pressure of lower pressure refrigerant circuit Unused Accumulated operation time of the pump Accumulated operation time of the fan Accumulated operation time of the compressor Accumulated operation...

Страница 69: ...1 0 o C 33 8 F 7 Changing of circulating fluid discharge pressure rise A STP Detection pressure for circulating fluid discharge pressure rise 0 55MPa 80PSI 6 Changing of circulating fluid discharge p...

Страница 70: ...tion speed 9 6 7 BCC ON 7 Data length 8BIT 7 Parity check NON 7 Stop bit length 2BIT 7 Response delay time 0 8 Communication range RW 7 Contact input output communication Contact input signal 1 RUN Co...

Страница 71: ...t temperature and the set temperature are displayed on the digital display Alarm menu screen is displayed when any alarm is generated See 5 4 PV SV Setting Circulating fluid temperature 2 Change the s...

Страница 72: ...shown on the alarm menu display The alarm display appears when an alarm is generated When multiple alarms are generated the latest alarm is displayed on the display Each time the SEL key is pressed th...

Страница 73: ...gher pressure side of the refrigerant circuit Refrigerant circuit pressure on the low pressure side Displays the pressure on the lower pressure side of the refrigerant circuit Unused Accumulated opera...

Страница 74: ...of the inlet refrigerant temperature to the compressor appears on the digital display PV SV Displays the refrigerant temperature at the compressor inlet port Checking Circulating fluid discharge press...

Страница 75: ...5 2 Time display Accumulated time Displayed value 0h to 999h to 1 000h to 99 999h to 100 000h Return to AL28 Pump maintenance alarm is generated when the accumulated operating time of the pump reache...

Страница 76: ...ting time of the thermo chiller appears on the digital display PV SV Refer to Table 5 5 2 for the display Checking Accumulated operating time of the dust proof filter 11 Press the SEL key once Display...

Страница 77: ...on can be started stopped by operating the RUN STOP key even when the button lock is being activated If you try to change the set value with the key or key while the button lock function is activated...

Страница 78: ...are available OFF 1 Press and hold the MENU key for approximately 2 seconds Repeat pressing the key until the button lock setting screen appears on the digital display PV SV PV SV PV SV Setting checki...

Страница 79: ...operate DIO REMOTE and SERIAL mode operation stop signals have priority Run timer Run timer starts operation after the set time If the thermo chiller is already operating or the pump is operating ind...

Страница 80: ...s Set to stop after 5 5 hours Now 1H 2H 3H 4H 5H 6H 7H 8H Stopped Operating Stopped Operating Stopped Run timer Stop timer Set to stop after 2 hours Set to start after 5 5hours Now 1H 2H 3H 4H 5H 6H 7...

Страница 81: ...or checking instructions of the timer that is to be used 1 Press and hold the MENU key for approximately 2 seconds Repeat pressing the button until the key lock setting display appears on the digital...

Страница 82: ...lanation Default Timer OFF to The product will stop automatically after the lapse of set time Setting unit 0 5 hours For example Stop timer setting performed at 4 30 PM to stop the product operation 1...

Страница 83: ...s being used Refer to the Communications Operation Manual for further details An example is shown below Set circulating fluid temperature 20 o C READY bandwidth range between the upper and lower limit...

Страница 84: ...Sets time for ready completion TEMP READY signal 1 Press and hold the MENU key for approximately 2 seconds Repeat pressing the key until the button lock setting display appears on the digital display...

Страница 85: ...irculating fluid temperature Setting temperature unit for Centigrade 0 1 o C Setting temperature unit for Fahrenheit 0 1 o F Fahrenheit to Setting checking READY time 6 Press the SEL key once Setting...

Страница 86: ...the circulating fluid temperature the circulating fluid temperature after offset which is displayed on the thermo chiller Table 5 9 1 Offset function Offset function Circulating fluid display temperat...

Страница 87: ...function and set the offset temperature to 1 0 o C 1 The thermo chiller controls the circulating fluid temperature aiming at 31 o C set circulating fluid temperature plus offset temperature 2 The dis...

Страница 88: ...the circulating temperature supplied to the user s equipment Use MODE 3 of the offset function and set the offset temperature to 1 0 o C 1 The thermo chiller controls the circulating fluid temperatur...

Страница 89: ...ffset temperature 0 0 o C 1 Press and hold the MENU key for approximately 2 seconds Repeat pressing the key until the button lock setting screen appears on the digital display PV SV PV SV PV SV Settin...

Страница 90: ...fset temperature is set Setting temperature unit for Centigrade 0 1 o C Setting temperature unit for Fahrenheit 0 1 o F Fahrenheit to 6 Press the MENU key once Returns to the main display which shows...

Страница 91: ...failure etc this function restarts the operation when the power supply restores retaining the conditions before the power cut When communication is being used If the communication mode is DIO REMOTE...

Страница 92: ...pressing the key until the key lock setting screen appears on the digital display PV SV PV SV PV SV Setting Checking Operation restoration after power failure function 2 Press the SEL key 8 times Set...

Страница 93: ...ps operation automatically Repeated automatic operation start and stop of the pump maintains the circulating fluid temperature to 3 o C to 3 o C to prevent the circulating fluid from being frozen When...

Страница 94: ...circulate when the pump starts automatic operation In extremely cold weather the heat generated by the pump operation may not be enough to prevent freezing of the circulating fluid During the automati...

Страница 95: ...mately 2 seconds Repeat pressing the key until the key lock setting screen appears on the digital display PV SV PV SV PV SV Setting Checkign Anti freezing function 2 Press the SEL key 9 times Setting...

Страница 96: ...und Sets button operation sound ON OFF ON 1 Press and hold the MENU button for approximately 2 seconds Repeat pressing the button until the button lock setting screen appears on the digital display PV...

Страница 97: ...ge Display Item Contents Default Temperature unit Sets temperature unit o C 1 Press and hold the MENU key for approximately 2 seconds Repeat pressing the key until the key lock setting screen appears...

Страница 98: ...Item Contents Default setting Pressure unit Sets pressure unit MPa 1 Press and hold the MENU key for approximately 2 seconds Repeat pressing the key until the key lock setting screen appears on the di...

Страница 99: ...Press and hold the MENU button for approximately 2 seconds Repeat pressing the button until the button lock setting screen appears on the digital display PV SV PV SV PV SV Data reset 2 Press the SEL...

Страница 100: ...operating time from the beginning 5 16 2 How to operate accumulated operating time reset function The table below shows the details of the accumulated operating time to be reset and the default setti...

Страница 101: ...set Resets the accumulated operating time of the pump Reset of accumulated operating time of the fan 4 Press and hold the MENU key for approximately 2 seconds Repeat pressing the key until the key loc...

Страница 102: ...y PV SV PV SV PV SV 8 Press the SEL key 16 times Resetting screen of the compressor accumulated operating time appears on the digital display PV SV 9 Select with key or key and press SEL key to enter...

Страница 103: ...y PV SV PV SV PV SV 11 Press the SEL key 29 times Resetting screen of the accumulated operating time of the dust proof filter appears on the digital display PV SV 12 Select with key or key and press S...

Страница 104: ...the warming up function is set ON the RUN light repeats turning ON for 0 5 seconds and OFF for 3 seconds while it is on standby when the pump is not operating The RUN light blinks every 0 3 seconds du...

Страница 105: ...at pressing the key until the key lock setting screen appears on the digital display PV SV PV SV PV SV Setting Checking Warming up function 2 Press the SEL key 26 times Setting screen of warming up fu...

Страница 106: ...ing up temperature Set value Explanation Initial value Default setting Setting and checking are not available when the warming up function is set OFF Centigrade to Sets the warming up temperature Sett...

Страница 107: ...s Initial value Default setting Alarm buzzer sound Sets alarm buzzer sound ON OFF ON 1 Press and hold the MENU key for approximately 2 seconds Repeat pressing the key until the alarm buzzer setting sc...

Страница 108: ...Impossible to select 1 Fan when the anti snow coverage function is ON operates as explained in 5 19 Anti Snow Coverage Function 2 The alarm operations of all the object alarms of the P RUN cannot be c...

Страница 109: ...irculating fluid discharge pressure rise Set pressure 0 55MPa 80PSI 7 0 05 to 0 6MPa 7 to 87PSI AL09 Circulating fluid discharge pressure drop Set pressure 0 05MPa 7PSI 8 0 05 to 1 00MPa 7 to 145PSI A...

Страница 110: ...line fuse cut AL22 Circulating fluid discharge temp sensor failure AL23 Circulating fluid return temp sensor failure AL24 Compressor suction temp sensor failure AL25 Circulating fluid discharge pressu...

Страница 111: ...mpressor over current AL47 Pump over current AL50 Incorrect phase error AL51 Phase board over current 12 Water cooled type model does not generate this alarm When the operation setting for the alarm t...

Страница 112: ...or Detection temp for the circulating fluid discharge temp drop alarm Alarm threshold 1 0 o C 33 8 o F Operation setting when Circulating fluid discharge pressure rise alarm is generated AL08 Circulat...

Страница 113: ...rge temp drop Range over detection timer AL03 Circulating fluid discharge temp rise An alarm will not be generated for the set period of time after the circulating fluid discharge temperature becomes...

Страница 114: ...n while the alarm is being generated OFF Operation setting during maintenance of the fan AL29 3 Fan maintenance Alarm operation OFF Operation setting during maintenance of the compressor AL30 Compress...

Страница 115: ...nerated Set value Explanation Initial value Default setting Operation continues when this alarm is generated Operation stops when this alarm is generated Setting Checking Operation setting when Circul...

Страница 116: ...alarm is set OFF Centigrade to Sets threshold detecting temperature for Circulating fluid discharge temp rise alarm Setting temperature unit for Centigrade 0 1 o C Setting temperature unit for Fahren...

Страница 117: ...en the Circulating fluid discharge temp drop alarm is set OFF Centigrade to Sets threshold detecting temperature for Circulating fluid discharge temp drop alarm Setting temperature unit for Centigrade...

Страница 118: ...to enter Table 5 19 14 Threshold detecting pressure setting for Circulating fluid discharge pressure rise alarm Set value Explanation Initial value Default setting Setting checking of the alarm is imp...

Страница 119: ...scharge pressure drop alarm 18 Press the SEL key once Threshold detecting pressure setting screen for Circulating fluid discharge pressure drop alarm generation appears on the digital display PV SV 19...

Страница 120: ...when this alarm is generated Setting Checking Threshold monitoring time setting for Communication error 22 Press the SEL key once Monitoring time setting screen for Communication error alarm appears...

Страница 121: ...al detection alarm is generated 26 Press the SEL key once Operation setting screen when Contact input 2 signal detection alarm is detected appears on the digital display PV SV 27 Set the product opera...

Страница 122: ...n the ambient temperature is out of the range between the temperatures set for AS 04 and AS 06 AL 03 or AL 04 may be generated at the same time when the product is turned ON Automatic monitoring When...

Страница 123: ...o Sets the time when alarm monitoring starts Setting unit is 1 minute Settings of this function and example of alarm generating timing for 5 19 3 Setting of temperature alarm monitoring method and ala...

Страница 124: ...ulating fluid temperature ON OFF 250sec 500sec Elapsed time AS 04 set temperature 16oC AS 06 set temperature 14oC 1 2 4 3 5 6 AS 06 Alarm monitoring Fig 5 3 Alarm generation timing Alarm generation ti...

Страница 125: ...Circulating fluid temperature Elapsed time Fig 5 4 Alarm generation timing Alarm generation timing Status 1 Start operation of the chiller As the circulating fluid temperature is within the set range...

Страница 126: ...essor suction temp AL11 Low compressor suction temp AL12 Low super heat temperature AL13 High compressor discharge pressure AL15 Refrigerant circuit pressure high pressure side drop AL16 Refrigerant c...

Страница 127: ...generated Set value Explanation Initial value Default setting This alarm signal is not detected While this setting is ON ALARM light on the operation panel keeps blinking with the light ON for 0 5 sec...

Страница 128: ...nerated Set value Explanation Initial value Default setting This alarm signal is not detected Operation continues when this alarm signal is generated Setting Checking Operation setting when Compressor...

Страница 129: ...ting when Dust proof filter maintenance alarm is generated Set value Explanation Initial value Default setting This alarm is not detected Operation continues when this alarm is generated Setting Check...

Страница 130: ...m is generated is displayed on the digital display SV PV 51 Set the monitoring time before the Dust proof filter maintenance alarm is generated with key or key and press SEL key to enter Table 5 19 33...

Страница 131: ...ALT Contact input signal 1 Delay timer time delay of reading Sets the delay timer of reading of contact input signal 1 0 2 Contact input signal 1 OFF detection timer Sets the contact input signal 1 O...

Страница 132: ...be performed on the operation panel Sets DIO mode 1 The product is operated with contact input output Sets SERIAL mode 2 Operation and setting are performed by serial communication 1 When the contact...

Страница 133: ...g Communication specification 5 Press the SEL key once Setting screen of the communication specification is displayed on the digital display PV SV 6 Select communication specification with key or key...

Страница 134: ...Slave address setting for MODBUS Setting range 1 to 99 Setting Checking Communication speed MODBUS 11 Press the SEL key once Setting screen of the communication speed MODBUS is displayed on the digita...

Страница 135: ...cking Communication speed simple communication protocol 15 Press the SEL key once Setting screen of communication speed simple communication protocol is displayed on the digital display PV SV 16 Set c...

Страница 136: ...communication protocol 19 Press the SEL key once Setting screen of data length simple communication protocol is displayed on the digital display PV SV 20 Set data length simple communication protocol...

Страница 137: ...mber Setting Checking Stop bit simple communication protocol 23 Press the SEL key once Setting screen of stop bit simple communication protocol is displayed on the digital display PV SV 24 Set stop bi...

Страница 138: ...nication range simple communication protocol 27 Press the SEL key once T Setting screen of communication range simple communication protocol is displayed on the digital display PV SV 28 Set communicat...

Страница 139: ...mplified communication protocol 2 External switch signal cannot be set Setting Checking Contact input signal 1 type 31 Press the SEL key once Setting screen of contact input signal 1 type is displayed...

Страница 140: ...cking Contact input signal 1 OFF detection timer 35 Press the SEL key once Setting screen of contact input signal 1 OFF detection timer is displayed on the digital display PV SV 36 Set threshold time...

Страница 141: ...te signal Setting Checking Contact input signal 2 type 39 Press the SEL key once Setting screen of contact input signal 2 type is displayed on the digital display PV SV 40 Select contact input signal...

Страница 142: ...ing Contact input signal 2 OFF detection timer 43 Press the SEL key once Setting screen of contact input signal 2 OFF detection timer is displayed on the digital display PV SV 44 Set threshold time fo...

Страница 143: ...ration stop timer setting status signal output Operation restoration from power failure setting status signal output Anti freezing setting status signal output Pass through signal output of the contac...

Страница 144: ...ct output signal 1 with key or key and press SEL key to enter Table 5 20 26 Setting of the alarm selected for the contact output signal 1 Set value Explanation Initial value Default setting Setting ch...

Страница 145: ...Operation stop timer setting status signal output Operation restoration from power failure setting status signal output Anti freezing setting status signal output Pass through signal output of the con...

Страница 146: ...ct output signal 2 with key or key and press SEL key to enter Table 5 20 29 Setting of the alarm selected for the contact output signal 2 Set value Explanation Initial value Default setting Setting ch...

Страница 147: ...s signal output Operation stop timer setting status signal output Operation restoration from power failure setting status signal output Anti freezing setting status signal output Pass through signal o...

Страница 148: ...et the alarm selected for the contact output signal 3 with key or key and press SEL key to enter Table 5 20 32 Setting of an alarm selected for the contact output signal 3 Set value Explanation Initia...

Страница 149: ...ater piping 6 1 1 Option M DI water Pure water piping This option is for customers who use DI water pure water as circulating fluid Circulating fluid wetted materials Stainless Include heat exchanger...

Страница 150: ...in the tank Automatic fluid filling does not start when alarm of table 5 19 1 is generated Fluid filling stops if the filling is automatic Table 6 2 1 Table of alarms automatic fluid filling stops doe...

Страница 151: ...ation Manual Communication Function for more details It is possible to read the alarm status using serial communication Refer to the Operation Manual Communication Function for more details This produ...

Страница 152: ...is the latest alarm The alarm with the largest number is the alarm that was generated first Example of display PV SV PV SV PV SV SEL SEL SEL When the alarms are generated in the order of AL16 AL03 and...

Страница 153: ...Press the and buttons simultaneously and the alarm buzzer stops Tips Alarm buzzers can be set not to make sound Refer to 5 1520 Alarm Buzzer Sound Setting It is not necessary to follow the buzzer sto...

Страница 154: ...el displays the circulating fluid temperature and the set circulating fluid temperature Contact signal output for contact input output communication stops Refer to the Operation Manual Communication F...

Страница 155: ...ermal operation switch is operated AL08 Circulating fluid discharge pressure rise A STP Check that there is no bending collapse or clogging with the external piping EEEE shown on the PI display in the...

Страница 156: ...displayed on the PI display of the main display and check monitor display Ask for service for the pressure sensor AL26 Compressor discharge pressure sensor failure P RUN Short circuit or broken wire o...

Страница 157: ...there is no power failure such as ground fault short circuit voltage fluctuation abnormal interphase voltage open phase surge Release the compressor thermal trip referring to 7 3 2 How to release the...

Страница 158: ...f the customer s power supply facility 2 Remove 12 screws to remove the upper panel Fig 7 1 Removal of upper panel 3 Remove 7 screws to remove the panel for electrical unit Fig 7 2 Remove the panel of...

Страница 159: ...sh the reset buttan If the circuit protector tripped make it ON by pushing up the lever Fig 7 3 Thermal relay and circuit protector location and statuses 5 Fasten the front cover of the electrical uni...

Страница 160: ...ker of the customer s power supply facility 2 Remove 12 screws to remove the upper panel Fig 7 4 Removal of upper panel 3 Remove 15 screws to remove the Left side panel Fig 7 5 Removal of Left side pa...

Страница 161: ...switch directly under the cover the switch is tripped If you press the switch from the cover and you do not feel the switch head directly under the cover the tripping is released You can not see if th...

Страница 162: ...rn ON the breaker The breaker of the user s power supply or the optional breaker has failed Replace the breaker No power supply e g Breaker s in the power supplying route has not been turned ON Supply...

Страница 163: ...ess Copper mg L 0 1 or less 0 3 or less Sulfide ion mg L Not detected Not detected Ammonium ion mg L 0 1 or less 1 0 or less Residual chlorine mg L 0 3 or less 0 3 or less Separation carbonic acid mg...

Страница 164: ...e operation panel There should be no problem for operation Circulating fluid flow rate Check on the operation panel There should be no problem for operation If flow rate has become smaller check for a...

Страница 165: ...h a long bristled brush or by air blow to prevent the fins from being deformed or damaged Removal of the dust proof filter 1 The dust proof filters are installed on the front and left sides of the pro...

Страница 166: ...eriodically Ensure that the water has not been contaminated and that there is no algae growth Circulating water inside the tank must be clean and there must not be foreign matter inside Use clean wate...

Страница 167: ...as an accessory for piping clean the screen mesh inside the strainer at the same time as when replacing the circulating fluid Ensure that there is no circulating fluid in the thermo chiller user s equ...

Страница 168: ...replace the mechanical seal Order the mechanical seal described in 8 3 Consumables as a service part Fig 8 3 Check for water leakage from pump Leakage from the mechanical seal It is impossible to prev...

Страница 169: ...e with heat generated by automatically operating the pump in the winter season or at night When the time required for increasing the temperature of the circulating fluid needs to be shortened at start...

Страница 170: ...Earth leakage breaker 2 Discharge all the circulating fluid completely from the thermo chiller Please refer to 8 4 1 Discharge of the circulating fluid for the method of drain the circulating fluid fr...

Страница 171: ...rn port 6 After discharging the circulating fluid from the drain port remove residual liquid in the tank using a syringe or waist cloth 7 Close the ball valve and mount the tank lid How to connect to...

Страница 172: ...the facility water piping 3 Remove the facility water piping from the product 4 Open the Left side panel then open the air vent valve The facility water in the product will be drained from the facili...

Страница 173: ...strainer 40 meshes 25A Barrel nipple 25A Anchor brackets 2pcs including M10 bolts 4pcs 9 Weight dry condition kg Approx 136 1 Use 15 ethylene glycol aqueous solution if operating in a place where the...

Страница 174: ...rainer 40 meshes 25A Barrel nipple 25A Anchor brackets 2pcs including M10 bolts 4pcs 8 Weight dry condition kg Approx 136 Compliance standard CE Marking EMC directive 2004 108 EC Machinery directive 2...

Страница 175: ...Alarm cord list label 2pc English 1pc Japanese 1pc Operation manual 2pc English 1pc Japanese 1pc Y strainer 40 meshes 25A Barrel nipple 25A Anchor brackets 2pcs including M10 bolts 4pcs 9 Weight dry c...

Страница 176: ...B A 65 Accessory Alarm cord list label 2pc English 1pc Japanese 1pc Operation manual 2pc English 1pc Japanese 1pc Y strainer 40 meshes 25A Barrel nipple 25A Anchor brackets 2pcs including M10 bolts 4p...

Страница 177: ...t Global Warming Potential GWP Regulation EU No 517 2014 Based on the IPCC AR4 Revised Fluorocarbons Recovery and Destruction Law Japanese law R134a 1 430 1 430 R404A 3 922 3 920 R407C 1 774 1 770 R41...

Страница 178: ...02 Chapter 9 Documents 9 2 Outline dimensions HRS090 Series 9 6 9 2 Outline dimensions 9 2 1 HRS090 A 20 40 Fig 9 1 Outline dimensions Dimensions for the positions of the anchor bolts View a a Power s...

Страница 179: ...HRX OM T002 Chapter 9 Documents HRS090 Series 9 2 Outline dimensions 9 7 9 2 2 HRS090 W 20 40 Fig 9 2 Outline dimensions Dimensions for the positions of the anchor bolts View a a Power supply 40...

Страница 180: ...d circuit Tank TS PS TS Customer s machine Heat load Fig 9 3 Flow diagram HRS090 A 20 40 9 3 2 HRS090 W 20 40 E E PS TS TS PS Compressor Expansion valve B Expansion valve A Dryer Press sensor Ref high...

Страница 181: ...mperature o C Cooling capacity kW 0 2 4 6 8 10 12 5 10 15 20 25 30 35 Circulating fluid temperature o C Cooling capacity kW Ambient temperature 32 o C Ambient temperature 40 o C Ambient temperature 45...

Страница 182: ...W 20 40 Fig 9 7 Pump capacity HRS090 A W 20 40 0 0 1 0 2 0 3 0 4 0 5 0 10 20 30 40 50 60 70 Circulating fluid flow L min Pressure MPa 0 10 20 30 40 50 Lifting head m Usable range 50Hz Circulating flui...

Страница 183: ...d sufficiently This symbol stands for a possible risk of electric shock The product is operated at high voltage and contains uncovered live terminals inside DO NOT operate the product without cover pa...

Страница 184: ...ts 9 6 Types of hazard labels HRS090 Series 9 12 9 6 1 Locations of Hazard Labels There are various warning labels on the product to show the potential hazards Fig 9 8 Locations of Hazard Labels Fig 9...

Страница 185: ...RS090 Series 9 7 Compliance standard 9 13 9 7 Compliance standard This system conforms to the following standards Table 9 5 Compliance standard Standard Model CE Mark EMC Directive Machinery Directive...

Страница 186: ...l Bussy Saint Georges F 77600 Germany SMC Pneumatik GmbH 49 6103 402 0 Boschring 13 15 D 63329 Egelsbach Greece SMC Hellas E P E 30 210 2717265 Anagenniseos 7 9 P C 14342 Nea Philadelphia Athens Hunga...

Страница 187: ...r Daily Check Sheet Model no Mfg code Operation conditions Presence of error Present Not present outlet press MPa Supply press MPa Flow rate L min Supply temp Discharge press MPa Temperature Fluid amo...

Страница 188: ...HRX OM T002 Chapter 9 Documents 9 9 Daily Check Sheet HRS090 Series 9 16...

Страница 189: ...The failure was a secondary failure of the product caused by the failure of equipment connected to the product 6 The failure was caused by a natural disaster such as an earthquake typhoon or flood or...

Страница 190: ...form checks and maintenance daily checks and regular checks specified in the Operation Manual and Maintenance Manual 3 Record the check and maintenance results on the daily check sheet attached to the...