HRX-OM-O021
Chapter 6 Alarm indication and trouble shooting
6.4
Other Errors
HRS Series
6-6
Table 6-2 Alarm code list and Troubleshooting (1/2)
Code
Descriptioin
Operation
Cause / Remedy
(Press the reset key after eliminating the cause.)
AL31
∗
3
Contact input1 signal
detection
∗
3
AL32
∗
3
Contact input 2 signal
detection
∗
3
Stop
∗
1
Contact input is detected.
AL33
Water leakage
Stop
∗
1
・
Check if the leakage sensor is connected.
・
Leakage occurred. Check the leakage point.
AL34
Electric resistivity rise
Continued
Electrical resistivity is larger than the set value.
AL35
Electric resistivity drop
Continued
Electrical resistivity is smaller than the set value.
Replace the DI filter.
AL36
DI sensor error
Continued
・
Check if the resistivity sensor is connected.
・
There may be short circuit or open wire of the resistivity
sensor. Replace the sensor.
∗
1
:
’’Stop” or “Continued” are default settings. The user can change them to “Continued” and “Stop”. For details, refer
to ’’5.15 Alarm customize function’’.
∗
2:”AL19, Communication error” is disabled in the default setting. When this function needs to be enabled, refer
to ’’5.18 Communication function’’.
∗
3
:
The functions of “AL31 Contact input 1 Signal detection” and “AL32 Contact input 2 Signal detection” are not
default settings. If these functions are used, refer to “5.18Communication function”.
∗4
: For air-cooled type.
6.4 Other Errors
How to check other errors
The causes and remedies for failures that are not indicated by alarm
numbers are shown in ’’Table 6-3
’’.
Table 6-3 Causes and remedies for failures without alarm number
Content of failure
Cause
Remedy
The breaker is not turned on.
Turn on the breaker.
Failure of
the
breaker.
Replace the breaker.
No power supply
(The breaker for the power supply
is not turned on.)
Supply the power.
The operation panel
displays nothing
Trip of breaker due to short-circuit
and current leakage
Repair the short-circuit or current
leaking part.
Communication is set.
Check the presence of communication
setting.
Failure of the [RUN] LED
Replace the controller.
The [RUN] LED does
not light up even when
the [RUN/STOP] switch
is pressed.
Failure of the [RUN/STOP] switch
Replace the controller.