HRX-OM-O021
Chapter 5 Display and setting of various functions
5.15
Alarm customize function
HRS Series
5-44
30.
Select the changing of DC line fuse cut from the table below with [
▲
] key or [
▼
] key,
and confirm by pressing “SEL”.
Table
5.15-16
List of set value
Set value
Explanation
Initial value
(Default setting)
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
○
Changing of
water leakage Sett
ing and checking
31.
Press the [SEL] key once.
The set screen of the changing of water leakage is displayed on the digital display.
PV
SV
32.
Select the changing of water leakage from the table below with [
▲
] key or [
▼
] key, and
confirm by pressing “SEL”.
Table
5.15-17
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of the water leakage option is OFF.
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
○
Changing of
electric resistivity rise
Sett
ing and checking
33.
Press the [SEL] key once.
The set screen of the changing of electric resistivity rise is displayed on the digital
display.
PV
SV