HRX-OM-O021
Chapter 5 Display and setting of various functions
HRS Series
5.15
Alarm customize function
5-43
25.
Select the changing of contact input signal 1 detection from the table below with [
▲
]
key or [
▼
] key, and confirm by pressing “SEL”.
Table 5.15-14
List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
○
Changing of
Contact input signal 2 detection
Setting and checking
26.
Press the [SEL] key once.
The set screen of the changing of contact input signal 2 detection is displayed on the
digital display.
PV
SV
27.
Select the changing of contact input signal 2 detection from the table below with [
▲
]
key or [
▼
] key, and confirm by pressing “SEL”.
Table 5.15-15
List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
○
28.
Press the [MENU] key once.
Return to the main screen (screen displaying the circulating fluid temperature).
PV
SV
Changing of
DC line fuse cut
Setting and checking
29.
Press the [SEL] key once.
The set screen of the changing of DC line fuse cut is displayed on the digital display.
PV
SV
Содержание HRS050-A*-20 Series
Страница 16: ...HRX OM O021 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS Series 1 10 ...
Страница 44: ...HRX OM O021 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS Series 3 24 ...
Страница 145: ...HRX OM O021 Chapter 8 Documents HRS Series 8 2 Outline dimensions 8 3 8 2 Outline dimensions Fig 8 1 Outline dimensions ...
Страница 155: ......