HRX-OM-W058
Chapter 5 Display and setting of various functions
5.16
Alarm customize function
HRS-R Series
5-36
5.16.2 Alarm customize function setting and checking
The table below explains the setting items of the alarm customize function
and the initial values.
Table 5.16-1
List of set alarm customize function(1/2)
Display
Item
Contents
Initial value
(Default setting)
Changing of low tank level
Set the operation when alarm No. AL01 "Low
tank level" is generated.
A.STP
Changing of circulating
fluid
discharge
temperature rise
Set the operation when alarm No. AL03
"circulating fluid discharge temperature rise" is
generated.
A.RUN
Detection temperature for
circulating fluid discharge
temperature rise
Sets the detection temperature for the alarm of
alarm NO. AL03 "circulating fluid discharge
temperature rise ".
Alarm signal is generated when the temperature
becomes higher than this temperature.
45.0
o
C
(113.0
o
F)
Changing of circulating
fluid
discharge
temperature drop
Set the operation when alarm No. AL04"
circulating fluid discharge temperature drop
“is
generated.
A.RUN
Detection temperature for
circulating fluid discharge
temperature drop
Sets the detection temperature for the alarm of
alarm NO. AL04 "circulating fluid discharge
temperature drop ".
Alarm signal is generated when the temperature
becomes lower than this temperature.
1.0
o
C
(33.8
o
F)
Changing of circulating
fluid discharge pressure
rise
Set the operation when alarm No. AL08
"circulating fluid discharge pressure rise " is
generated.
A.RUN
Detection
pressure
for
circulating fluid discharge
pressure rise
Sets the detection pressure for the alarm of alarm
NO. AL08 "circulating fluid discharge pressure
rise ".
Alarm signal is generated when the pressure
becomes higher than this pressure.
0.30MPa
(44PSI)
Changing of circulating
fluid discharge pressure
drop
Set the operation when alarm No. AL09
"circulating fluid discharge pressure drop" is
generated.
A.RUN
Detection
pressure
for
circulating fluid discharge
pressure drop
Sets the detection pressure for the alarm of alarm
NO. AL09 "circulating fluid discharge pressure
drop ".
Alarm signal is generated when the pressure
becomes lower than this pressure.
0.05MPa
(7PSI)
Changing
of
operation
when communication error
Set the operation when the alarm No. AL19
“Communication error” is generated.
OFF
The monitoring time of
communication error
Set the alarm monitoring time when the alarm No.
AL19 “Communication error” is generated. Alarm
signal is generated when the monitoring time is
exceeded.
30 sec
Changing of contact input
signal 1 detection
Set the operation when the alarm No. AL31
“contact input signal 1 detection” is generated.
A.STP
Changing of contact input
signal 2 detection
Set the operation when the alarm No. AL32
“contact input signal 2 detection” is generated.
A.STP
Changing of DC line fuse
cut
Set the operation when the alarm No. AL21
“DC
line fuse cut
” is generated.
A.STP
Unused
- - - -
*1
Unused
- - - -
*1
Unused
- - - -
*1
Содержание HRS018-A*-20-*
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......