HRX-OM-W058
Chapter 5 Display and setting of various functions
5.16
Alarm customize function
HRS-R Series
5-48
When "Automatic moni Monitoring start timer" is selected
[1] Circulating fluid temperature when starting operation: Approximately 20
o
C
[2]
Circulating fluid set temperature
: 15
o
C
[3] "AS.21: Temperature alarm monitoring method": Select "Automatic monitoring + Monitoring
start timer".
[4] "AS.22: Monitoring start timer": Set it to "50 min".
[5] "AS.04: Detection temp. for the circulating fluid discharge temp. increase": Set to "16
o
C".
[6] "AS.06: Detection temp. for the circulating fluid discharge temp. drop": Set to "14
o
C".
[7] "AS.23: Range over detection timer": Set to "600 sec".
Fig 5.16-2
Alarm generation timing
-Alarm generation timing
Status (1): Start operation of the chiller. As the circulating fluid temperature is within the set
range of "AS.06", "AS.06" alarm monitoring starts.
Status (2): The circulating fluid temperature becomes within the set range of "AS.04".
"AS.04" alarm monitoring starts.
Status (3): The circulating fluid temperature exceeds the threshold of "AS.06", but the alarm
will not be generated as it has returned within the 600 sec range of the "AS.23:
Range over detecting timer".
Status (4): The circulating fluid temperature exceeds the threshold of "AS.04", but the alarm
will not be generated as it has returned within the 600 sec range of the "AS.23:
Range over detecting timer".
Status (5): 50 minutes passes after starting operation. Alarm monitoring has started. It
shows that the "50 min" setting does not influence the alarm monitoring under
these conditions.
Status (6): Alarm will be generated after 600 seconds that is set for "AS.23: Range over
detection timer" after the circulating fluid temperature exceeds the threshold of
"AS.04".
Thermo chiller
Run
Stop
Circulating fluid
set temperature 15
o
C
AS.04
Alarm monitoring
ON
OFF
Alarm
Generation
Nothing
50min
600sec
Circulating fluid
temperature
ON
OFF
250sec
500sec
Elapsed time
AS.04
set temperature 16
o
C
AS.06
set temperature 14
o
C
1
2
4
3
5
6
AS.06
Alarm monitoring
Содержание HRS018-A*-20-*
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......