HRX-OM-W058
Chapter 5 Display and setting of various functions
5.16
Alarm customize function
HRS-R Series
5-40
Changing of circulating fluid discharge pressure rise
Setting and checking
12.
Press the [SEL] key once.
The set screen of changing of circulating fluid discharge pressure rise is displayed on the
digital display.
13.
Select changing of circulating fluid discharge pressure rise from the table below with
[▲]
key or
[▼] key, and confirm by pressing “SEL”.
Table 5.16-8
List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
○
Operation is stopped when this alarm signal is
generated.
Detection temperature for circulating fluid discharge pressure rise
Setting and checking
14.
Press the [SEL] key once.
The set screen of detection temperature for circulating fluid discharge pressure rise is
displayed on the digital display.
15.
Select detection temperature for circulating fluid discharge pressure rise from the table
below with
[▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.16-9
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the setting of
the circulating fluid discharge pressure rise is OFF.
MPa
to
Sets detection temp for the circulating fluid
discharge pressure rise.
・
Option -T, -MT (100V)
Set range: 0.05 to 0.55MPa (7 to 80PSI)
Default setting: 0.55MPa (80PSI)
・
Option -T (200V)
Set range: 0.05 to 0.70MPa (7 to 102PSI)
Default setting: 0.70MPa (102PSI)
・
Option -MT (200V)
Set range: 0.05 to 0.60MPa (7 to 87PSI)
Default setting: 0.60MPa (87PSI)
Pressure unit is MPa: Setting unit is 0.01MPa
Pressure unit is PSI: Setting unit is 1PSI
PSI
to
PV
SV
PV
SV
Содержание HRS018-A*-20-*
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......