HRL
Series
Dual Channel Refrigerated Thermo-chiller for Lasers
Operation Display Panel
Alarm
Items shown on the touch panel home screen
No.
Classification
CH no.
Item
Explanation
Displayed
value
CH1
Circulating fluid temperature
It indicates the current temperature.
Circulating fluid set temperature
It indicates the set temperature.
Circulating fluid discharge pressure
It indicates the discharge pressure.
Circulating fluid
flow rate
It indicates the fluid flow rate. This value is not measured by a flow meter. It should be used as a
reference value (rough indication). It includes the flow rate in the bypass circuit.
CH2
Circulating fluid temperature
It indicates the current temperature.
Circulating fluid set temperature
It indicates the set temperature.
Circulating fluid discharge pressure
It indicates the discharge pressure.
Circulating fluid
flow rate
It indicates the flow rate measured by a flow meter.
It does not include the flow rate in the bypass circuit.
Circulating fluid electric conductivity
It indicates the electric conductivity.
Common Operating condition display It indicates the run and stop status of the product.
Button
CH1
Independent pump operation
CH1 pump operates independently while the button is pressed.
CH2
Independent pump operation
CH2 pump operates independently while the button is pressed.
Common Operation mode
To select a operation mode from the touch panel (
mode), contact input (
mode),
or serial communication (
mode).
Common Run/Stop
To run/stop the product
This unit displays 38 types of alarms.
Alarm
code
Indication
Explanation
AL01
CH1 Low Level FL
T
CH1 abno
rmal lo
w tank fluid l
evel
AL02
CH1 Low Level WRN
CH1 lo
w tank fluid l
evel
AL0
3
CH2 Low Level FL
T
CH2 abno
rmal lo
w tank fluid l
evel
AL04
CH2 Low Level WRN
CH2 lo
w tank fluid l
evel
AL06
Fan Inverter
Fan failure
AL09
CH1 High
T
emp. FL
T
CH1 abno
rmal r
ise of circulating fluid tempe
rature
AL10
CH1 High
T
emp.
CH1 circulating fluid tempe
rature rise
AL11
CH1 Low
T
emp.
CH1 circulating fluid tempe
rature drop
AL12
CH1
TEMP REA
DY Alarm
CH1
TEMP REA
DY alarm
AL1
3
CH2 High
T
emp. FL
T
CH2 abno
rmal r
ise in circulating fluid tempe
rature
AL14
CH2 High
T
emp.
CH2 circulating fluid tempe
rature rise
AL15
CH2 Low
T
emp.
CH2 circulating fluid tempe
rature drop
AL16
CH2
TEMP REA
DY Alarm
CH2
TEMP REA
DY alarm
AL17
CH1 HX In High
T
emp. FL
T
CH1 abno
rmal rise in heat exchanger inlet temperature
AL1
8
CH1 Pres
s. Sensor
CH1 f
ailure of circulating fluid discharge pressure sensor
AL19
CH1 High Pres
s.
CH1 circulating fluid discharge pressure
rise
AL20
CH1 Lo
w Pres
s.
CH1 circulating fluid discharge pressure drop
AL21
CH2 Pres
s. Sensor
CH2 f
ailure of circulating fluid discharge pressure sensor
AL22
CH2 High Pres
s. Error
CH2 abno
rmal r
ise in circulating fluid discharge pressure
Alarm
code
Indication
Explanation
AL2
3
CH2 High Pres
s.
CH2 circulating fluid discharge pressure
rise
AL24
CH2 Lo
w Pres
s.
CH2 circulating fluid discharge pressure drop
AL25
CH2 Lo
w Pres
s. Error
CH2 abno
r
mal drop in circulating fluid discharge pressure
AL26
CH2 Flow Sensor
CH2 f
ailure of circulating fluid discharge fl
ow sensor
AL27
CH2 High Electric Conductivity
CH2 electric conductivity increase
AL3
0
Digital Input 1
Contact input 1 signal detection
AL3
1
Digital Input 2
Contact input 2 signal detection
AL3
4
Communication
Communication error
AL35
Ambient
T
emp.
Outside of the ambient tempe
rature range
AL3
6
Maintenance
Maintenance ala
rm
AL3
7
Refrigeration Circuit
Compressor circuit failure
AL38
Sensor
Sensor failure
AL39
Controller
Controller failure
AL40
Compressor Inverter
Compressor inverter error
AL41
Compressor Inverter Comm. Compressor inverter communication error
AL42
CH1 Pump I
nverter
CH1 pump inverter error
AL43
CH1 Pump I
nverter Comm. CH1 pump inverter communication error
AL44
CH2 Pump I
nverter
CH2 pump inverter error
AL45
CH2 Pump I
nverter Comm. CH2 pump inverter communication error
15