![SMC Networks EX600-ED Series Скачать руководство пользователя страница 74](http://html1.mh-extra.com/html/smc-networks/ex600-ed-series/ex600-ed-series_operation-manual_1299354074.webp)
-73-
No.EX##-OMN0030-A
•Digital Input/Output Unit object (Class:70 h) [
DeviceNet
TM
extended object library 1]
Instance
Attribute
Access
Name
Type
Value
70h Get/Set
Monitoring short circuit at Power
Supply
BOOL
0=Disable
1=Enable
71h
Get/Set Monitoring short circuit at Output
BOOL
0=Disable
1=Enable
78h
Get/Set Inrush current detection
BOOL
0=Disable
1=Enable
7Bh
Get/Set Restart after short circuit
BOOL
0=Manual
1=Auto
A4h
Get/Set Input filtering time
USINT
0=0.1 ms
1=1.0 ms
2=10 ms
3=20 ms
01h to 40h
A8h
Get/Set Input extension time
USINT
0=1.0 ms
1=15 ms
2=100 ms
3=200 ms
•Analog Output Unit object (Class:71 h) [
DeviceNet
TM
extended object library 1]
Instance
Attribute
Access
Name
Type
Value
70h Get/Set
Monitor short circuit at Power
Supply
BOOL
0=Disable
1=Enable
A8h
Get/Set Ch0 analog range
USINT
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20 mA
7=4…20 mA
A9h
Get/Set Ch1 analog range
USINT
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20 mA
7=4…20 mA
01h to 10h
ACh
Get/Set Analog data format
USINT
0=Offset Binary
1=Sign and Magnitude
2=2’s complement
3=Scaled
Содержание EX600-ED Series
Страница 29: ...28 No EX OMN0030 A Dimensions...
Страница 33: ...32 No EX OMN0030 A EX600 ED3...