•Analog output unit parameters (1)
Parameter
setting
No.
Parameter
(H.T. Symbol)
Definition
Item
Content
Default
setting
By
EDS
By
H.T.
Enable Generates
an
error.
○
1
The power
supply short
circuit
detection for
the output
device
(SC_MonSs)
Generates error
per unit when the
short circuit of the
output device is
detected.
Disable
Does not generate an
error.
○
○
0..10 V
0..5 V
1..5 V
0..20 mA
2
Analog output
range
(Range)
Sets the range of
the analog output
device per channel.
4..20 mA
Selects the analog
output range.
0..10 V
○
○
Offset binary
Offset binary.
○
Sign & Magnitude
Signed binary.
2s complement
2’s complement.
3
Analog data
format
(D_Format)
Sets analog data
type which is
output to PLC per
unit.
Scaled
Scale conversion type.
○
○
Enable Generates
an
error.
∗
2
User setting
value upper
limit error
(Upr_Lmt)
Generates error
per channel when
the output value
exceeds the set
value.
Disable
Does not generate an
error.
○
Enable
Generates an error.
Val: -32766 to 32767
4
Scale upper
limit setting
∗
1
(UpLm/Scl)
Sets the scale
upper limit.
Generates error
per channel when
the output value
exceeds the upper
limit.
Disable
Does not generate an
error.
Val: -32766 to 32767
○
Val: 1000
∆
∗
5
○
Enable Generates
an
error.
∗
2
User setting
value lower
limit error
(Lwr_Lmt)
Generates error
per channel when
the output value
falls below the set
value.
Disable
Does not generate an
error.
○
Enable
Generates an error.
Val: -32767 to 32766
5
Scale lower
limit setting
∗
1
(LwLm/Scl)
Sets the scale
lower limit.
Generates error
per channel when
the output value
falls below the
lower limit.
Disable
Does not generate an
error.
Val: -32767 to 32766
○
Val: 0
∆
∗
5
○
Enable
Output will be user fault
value.
∗
2
6
Output setting
for
communication
fault
∗
3
(Fault_MA)
Set output per
channel when
communication is
abnormal.
Disable
Output will be held last
state.
○
∆
∗
5
○