![SMC Networks EX600-ED Series Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/smc-networks/ex600-ed-series/ex600-ed-series_operation-manual_1299354073.webp)
-72-
No.EX##-OMN0030-A
•Analog Input/Output Unit object (Class:6Fh) [
DeviceNet
TM
extended object library 1]
Instance
Attribute
Access
Name
Type
Value
70h Get/Set
Monitor short circuit at Power
Supply
BOOL
0=Disable
1=Enable
74h
Get/Set Monitor over range
BOOL
0=Disable
1=Enable
75h
Get/Set Monitor under range
BOOL
0=Disable
1=Enable
A4h
Get/Set I-Ch0 analog input filter
USINT
0=None
1=2 value average
2=4 value average
3=8 value average
A5h
Get/Set I-Ch1 analog input filter
USINT
0=None
1=2 value average
2=4 value average
3=8 value average
A8h
Get/Set I-Ch0 analog range
USINT
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20 mA
7=4…20 mA
A9h
Get/Set I-Ch1 analog range
USINT
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20 mA
7=4…20 mA
AAh Get/Set
O-Ch0
analog
range
USINT
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20 mA
7=4…20 mA
ABh Get/Set
O-Ch1
analog
range
USINT
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20 mA
7=4…20 mA
01h to 10h
ACh
Get/Set Analog data format
USINT
0=Offset Binary
1=Sign and Magnitude
2=2’s complement
3= Scaled