-22-
No.EX##-OMN0030-A
•V_SEL switch: A function to select the number of occupied valve outputs.
The number of outputs (size) occupied by the SI unit is selected.
Settings1
1
2
Content
SI unit output data size
OFF
OFF
Number of valves = 32 outputs
4 byte (Default setting)
OFF
ON
Number of valves = 24 outputs
3 byte
ON
OFF
Number of valves = 16 outputs
2 byte
ON
ON
Number of valves = 8 outputs
1 byte
∗
: Set the number of occupied valve outputs to at least the number of valves used.
•Baud Rate switch: Sets the communication speed of the internal bus of the product.
Settings1
3
4
Content
OFF
OFF
1 Mbps (Default setting)
OFF ON
500
kbps
ON OFF
250
kbps
ON ON
125
kbps
∗
: This function is for possible extension. Keep the default setting of 1 Mbps.