23-
4.1.1.
PressureValueMonitoring
The CH to be monitored is selected by the value contained in PressureValueMonitoringChannelSelection
(
). The CH monitor value is the output process data.
Table 4-3. PressureValueMonitoring
byte
1
0
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Sign
Pressure value
Table 4-4. Pressure value (Pressure range parameter : -100...100 kPa)
bit 15...0
Pressure
value[kPa]
0x0000 0.0
0x0001 0.1
...
...
0x03E7 99.9
0x03E8 100.0 or more
...
Unused
0x8000 Abnormal
...
Unused
0xFC18 -100.0 or less
0xFC19 -99.9
...
...
0xFFFE -0.2
0xFFFF -0.1
Table 4-5. Pressure value (Pressure range parameter : -100...200 kPa)
bit 15...0
Pressure
value[kPa]
0x0000 0.0
0x0001 0.1
...
...
0x07CF 199.9
0x07D0 200.0 or more
...
Unused
0x8000 Abnormal
...
Unused
0xFC18 -100.0 or less
0xFC19 -99.9
...
...
0xFFFE -0.2
0xFFFF -0.1
Note
The switching timing of the PressureValueMonitoring CH may differ between the process data of
the IO-Link and the process data of the upper communication.
Note
The table on the left shows an example when Pressure range parameter
(
) is set to -100...100 kPa for the selected CH.
The value is fixed at 0x8000 if selected CH does not exist, if Pressure
sensor use parameter (
) for selected CH set to Unused, if
pressure sensor has a short circuit, or if pressure sensor of selected CH
has a failure/disconnection.
0x03E9...0x7FFF and 0x8001...0xFC17 are unused.
Note
The table on the left shows an example when Pressure range parameter
(
) is set to -100...200 kPa for the selected CH.
The value is fixed at 0x8000 if selected CH does not exist, if Pressure
sensor use parameter (
) for selected CH set to Unused, if
pressure sensor has a short circuit, or if pressure sensor of selected CH
has a failure/disconnection.
0x07D1...0x7FFF and 0x8001...0xFC17 are unused.