Operation
8-8
06/18/04
8.5 Setting mode, Level 3
The method to enter to and return from setting mode Level 3 and which mode can be set in the level are
explained below.
8.5.1 How to enter and return
Press[SEL]and[ ]keys at the same time while power is turned on. Then, the indication on [MODE] is
changed depending on the number of press and the data in the indicated mode can be set. To return to
current temp. indication, press[RET]key twice.
When no input is done within 1 min. regardless of setting mode, the
current temp. indication is returned automatically.
8.5.2 Available mode in Level 3
The mode, which can be set in setting mode Level 3, is as shown on Table 8-3. The mode available in
Level 3 is supposed not to be used normally for the purpose other than initial setting and the setting
related to communication is included.
The data input in setting mode Level 3 is written into EEPROM and stored
when power is turned off. The limit of writing into EEPROM is 0.1 mil.
times.
Table8-3 Available mode in Level 3
No.
Modes
Setting contents
Setting range
(Min. increment)
Default
1
Unit Number
Sets the unit No. used. This is
applicable only when multiple Thermo-
con is used.
0 to F (Hex decimal)
0
2
Baud Rate
Sets baud rate for communication.
600,1200,2400,4800
9600,19200b/s
1200
3
Parity Bit
Sets parity bit for communication.
Without : No parity
Odd : Odd
Even : Even
Without,
Odd,
Even
Without
4
Data Length
Sets data length for communication.
7Bits,
8Bits
8
5
Stop Bit
Sets stop bit for communication.
1Bit,
2Bits
1