HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 54 of 60
14.6
CUMMINS QSM11
Table 29 - Engine OEM Connector
Terminals of controller
OEM connector of engine
Remark
Fuel relay output
38
Start relay output
-
Connect with starter coil directly
CAN GND
-
CAN communication shielding line (connect
with controller‘s this terminal only).
CAN(H)
46
Using impedance 120Ω connecting line.
CAN(L)
37
Using impedance 1
20Ω connecting line.
Engine type: common J1939
14.7
CUMMINS QSZ13
Table 30 - Engine OEM Connector
Terminals of controller
OEM connector of engine
Remark
Fuel relay output
45
Start relay output
-
Connect to starter coil directly
Auxiliary output 1
16&41
Setting to idle speed control, normally open
output. Making 16 connect to 41 during
high-speed running of controller via external
expansion relay.
Auxiliary output 2
19&41
Setting to pulse raise speed control,
normally open output. Making 19 connect
with 41 for 0.1s during high-speed warming
of controller via external expansion relay.
CAN GND
-
CAN communication shielding line (connect
with controller‘s this terminal only).
CAN(H)
1
Using impedance 120Ω connecting line.
CAN(L)
21
Using impedance 120Ω connecting line.
Engine type: Common J1939
14.8
DETROIT DIESEL DDEC III / IV
Table 31 - Engine CAN Connector
Terminals of controller
CAN port of engine
Remark
Fuel relay output
Expand 30A relay, battery
voltage of ECU is supplied
by relay.
Start relay output
-
Connect to starter coil directly.
CAN GND
-
CAN communication shielding line
(connect with controller‘s terminal only).
CAN(H)
CAN(H)
Using impedance 120Ω connecting line.
CAN(L)
CAN(L)
Using impedance 120Ω connecting line.
Engine type: Common J1939