![Smartgen HGM8110DC Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/smartgen/hgm8110dc/hgm8110dc_user-manual_1297526046.webp)
HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 46 of 60
9
PARAMETERS SETTING
CAUTION:
Please change the controller parameters when generator is in standby mode only (e. g. Crank
disconnect conditions selection, configurable input, configurable output, various delay), otherwise, shutdown and
other abnormal conditions may happen.
NOTE:
1) Maximum set value must over minimum set value in case that the condition of too high as well as too low
will happen.
2) When setting the warning alarm, please set the correct return value; otherwise, maybe there is abnormal
alarm. When setting the maximum value, the return value must less than set value; when setting the
minimum value, the return value must over set value.
3) Please set the generator frequency value as low as possible when cranking, in order to make the starter be
separated quickly as soon as crank disconnect.
4) Configurable input could not be set as same items; otherwise, there are abnormal functions. However, the
configurable output can be set as same items.