HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 48 of 60
11 COMMISSIONING
Please make the under procedures checking before commissioning,
— Ensure all the connections are correct and wires diameter is suitable.
— Ensure that the controller DC power has fuse, controller‗s positive and negative connected to start
battery are correct.
— Emergence stop must be connected with positive of start battery via scram button‘s normal close
point and fuse.
— Take proper action to prevent engine to crank disconnect (e. g. Remove the connection wire of fuel
valve). If checking is OK, make the start battery power on; choose manual mode and controller will
executive routine.
— Set controller under manual mode, press ―start‖ button, genset will start. After the setting times as
setting, controller will send signal of Start Fail; then press ―stop‖ to reset controller.
— Recover the action of stop engine start (e. g. Connect wire of fuel valve), press start button again,
genset will start. If everything goes well, genset will normal run after idle running (if idle run be set).
During this time, please watch for engine‘s running situations and AC generator‘s voltage and
frequency. If abnormal, stop genset running and check all wires connection according to this manual.
— If there is any other question, please contact SmartGen‘s service.