HGM6510 GENSET PARALLEL UNIT
HGM6510 Genset Parallel Unit
ISSUE 2013-07-15
Version 1.7
Page 33 of 52
Other parameters configuration (can only be configured via PC software)
Parameter
Default Value
Module Address
1
Alternator Selection
Yes
Poles
4
Magnetic Pickup
Yes
Quick On-load Mode
No
Start Times
3
Voltage Transformer
No
Fuel Pump Control
No
Input 1
Remote start on-load demand; close to activate
Input 2
Low oil pressure; close to activate; active period:
from safety on.
Input 3
High temperature; close to activate; active period:
from safety on.
Input 4
Generator Closed Auxiliary; close to activate
Input 5
Indication, close to activate
Input 6
Working mode selection, close to activate
Input 7
Indication, close to activate
Input 8
Indication, close to activate
Input 9
Indication, close to activate
Output 1
Generator Voltage Normal
Output 2
Common alarm
Output 3
Idle/high speed control
Output 4
Close Generator Pulse
Output 5
Open Generator Pulse
Generator Rated Frequency
50.0Hz
Generator Rated Voltage
230V
LED1
System in
AUTO
mode
LED2
Fail to start
LED3
Common shutdown
LED4
Common alarm
Delayed Over Current
100%(500A)
Time multiplier
36
Over Current Action
Trip and Stop
Crank Disconnect Generator
Frequency
15Hz
Crank Disconnect Engine Speed 450RPM
Crank Disconnect Oil Pressure
Not used
Detect Oil Pressure During
Cranking
No
Scheduled Start
No
MSC ID
0
GOV Settings
0V
AVR Settings
0V