Parameters list:
Parameter
Range
Default
Notes
01 Low Oil Pressure
(Warn)
(1-999)kPa 124kPa/18.0PSI
Return
value:
138kPa/20.0PSI
02 Low Oil Pressure
(Shutdown)
(0-997)kPa
103kPa/14.9PSI
Setting standard:
Shutdown
value<Warn
value<Return value
03 High Temperature
(Warn)
(81-139)ºC
90ºC/194ºF
Return value: 88°C/190°F
04 High Temperature
(Shutdown)
(82-140)ºC
95ºC/203ºF
Setting standard:
Shutdown
value<Warn
value<Return value
05
Low Fuel
Level
(Warn)
(0-100)%
10%
Analogue value
06 Start Delay
(0-9999)s
5s
Timer
07 Preheat Delay
(0-300)s
0s
Timer
08 Cranking Time
(3-60)s
8s
Timer
09 Crank Rest Time
(3-60)s
10s
Timer
10 Safety On Time
(1-60)s
10s
Timer
11
Over
Speed/
Overshoot delay
(0-10)s
2s
Timer
12 Start Idle Time
(0-3600)s
10s
Timer
13 Warming Up Time
(0-3600)s
30s
Timer
14 Stop Delay
(0-9999)s
30s
Timer
15 Cooling Time
(0-3600)s
60s
Timer
16 Stop Idle Time
(0-3600)s
10s
Timer
17 ETS Solenoid Hold
(0-120)s
2s
Timer
18 Fail to Stop Delay
(10-120)s
30s
Timer
19 Generator Transient
Delay
(0-30)s
5s
Timer
20 Battery Under Volt
Delay
(0-9999)s
60s
Timer
21 Battery Over Volt
Delay
(0-9999)s
60s
Timer
22
Reverse
Power
Delay
(0-300)s
10s
Timer
23 Generator Under Volt
(Warn)
(50-1300)V
196V
On-load value: 207V
Setting standard:
Shutdown
value<Warn
value<On-load value
24 Generator Under Volt
(Shutdown)
(50-1300 )V
184V
Generator under voltage
shutdown value
25 Generator Over Volt
(Warn)
(50-1300)V
265V
Return value: 253V
26 Generator Over Volt
(Shutdown)
(50-1300)V
273V
Setting standard:
Shutdown
value>Warn