HGM400N Series Genset Controller User Manual Page 38 of 38
13
FAULT FINDING
Table 13 Fault Finding
Symptom
Possible Remedy
Controller no response with
power
Check starting batteries;
Check controller connection wirings;
Check DC fuse.
Genset shutdown
Check the water/cylinder temperature is too high or not;
Check the genset AC voltage;
Check DC fuse.
Low oil pressure alarm after
crank disconnect
Check the oil pressure sensor and its connections.
High water temp. alarm after
crank disconnect
Check the water temperature sensor and its connections.
Shutdown alarm during running
Check related switch and its connections according to the
information on LCD;
Check auxiliary inputs.
Fail to Start
Check fuel circuit and its connections;
Check starting batteries;
Check speed sensor and its connections;
Refer to engine manual.
Starter no response
Check starter connections;
Check starting batteries.
Genset running while ATS not
transfer
Check ATS;
Check the connections between ATS and controllers.
___________________________________