HGM400N Series Genset Controller User Manual Page 15 of 38
No.
Items
Description
Sensor Open
level sensor is open circuit and the action selects “Shutdown”, it will initiate
a shutdown alarm and the corresponding alarm information will be
displayed on LCD.
22 High Temp. 2
When the controller detects that config. sensor temperature (sensor type:
temperature sensor) has exceeded the pre-set value, it will initiate a
shutdown alarm and the corresponding alarm information will be displayed
on LCD.
23 Low OP 2
When the controller detects that config. sensor oil pressure (sensor type: oil
pressure sensor) has fallen below the pre-set value, it will initiate a
shutdown alarm and the corresponding alarm information will be displayed
on LCD.
24 Low Coolant Level
When the controller detects that config. sensor fuel level (sensor type:
level sensor) has fallen below the pre-set value, it will initiate a shutdown
alarm and the corresponding alarm information will be displayed on LCD.
25 Maintenance Due
When genset running time has exceeded the user setting maintenance time
and the action selects “Shutdown”, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD. The maintenance
alarm will reset if the action selects “Inactive”.
26 Over Power
If over power detection is enabled, when the controller detects that the
power value (power is positive) has exceeded the pre-set value and the
action selects “Shutdown”, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.