HGM400N Series Genset Controller User Manual Page 16 of 38
6
CONNECTIONS
Compared with
HGM420N
,
HGM410N
has no Mains Voltage 3-phase input terminals. The rear panel of
HGM420N
is as below.
Fig.2 Controller Rear Panel
Table 6 Terminal Connection Description
Pin
Function
Cable Size
Description
1
B-
2.5mm
2
Connected with negative of starter battery.
2
B+
2.5mm
2
Connected with positive of starter battery. If wire
length is over 30m, better to double wires in parallel.
Max. 20A fuse is recommended.
3
Aux. Output 1
1.5mm
2
B+ is supplied by 2 point, rated
5A.
For details please
see Table 2.
4
Crank
1.5mm
2
B+ is supplied by 2 point, rated
5A.
5
Aux. Output 2
1.5mm
2
B+ is supplied by 2 point, rated
5A.
6
Aux. Output 3
1.5mm
2
B+ is supplied by 2 point, rated
5A.