HGM400N Series Genset Controller User Manual Page 22 of 38
No.
Items
Range
Default
Description
66
High
Temp. Inhibit
Enabled
(0-1)
0
Factory default: when high temperature occurs,
shutdown alarm is initiated.
67 Low OP Inhibit Enabled
(0-1)
0
Factory default: when low oil pressure occurs,
shutdown alarm is initiated.
68 Low Fuel Level Inhibit
(0-1)
1
Factory default: when low fuel level occurs,
shutdown alarm is initiated.
69 Config. Sensor Inhibit
(0-1)
1
Factory default: when config. sensor value
higher/lower than the set value (particular case
depends on the sensor type), warning alarm is
initiated. Functions see 66, 67, 68.
70 AC System
(0-3)
0
0: 3P4W; 1: 2P3W
2: 1P2W; 3: 3P3W
71 Temp. Sensor Curve
(0-12)
8
SGX Please see Table 10.
72 Pressure Sensor Curve
(0-12)
8
SGX Please see Table 10.
73
Multiplex Input Level
Sensor
(0-1)
0
0: Digital Input 3
1: Level Sensor
Please see Table 8.
NOTE 5
74 Level Sensor Curve
(0-7)
3
SGD Please see Table 10.
75
Multiplex Input Config.
Sensor
(0-3)
0
0: Digital Input 4
1: Temperature Sensor
2: Oil Pressure Sensor
3: Level Sensor
Please see Table 8.
NOTE 5
76 Config. Sensor Curve
(0-9)
(0-9)
(0-5)
8
8
3
SGX
SGX
SGD
77 Poles
(2-64)
4
Number of generator poles. It can be used for
calculating engine speed which without speed
sensor.
78
Temp. Sensor Open
Action
(0-2)
1
0: Indication (Corresponding sensor position
on the LCD will show “+++”);
1: Warn; 2: Shutdown
79 OP Sensor Open Action
(0-2)
1
80
Fuel Level Sensor Open
Action
(0-2)
1
81
Config. Sensor Open
Action
(0-2)
1
82 Cooling Blower On
(0-140)°C
60
It controls the cooling blower to open or close
if the output port is configured as Cooling
Blower.
83 Cooling Blower Off
(0-140)°C
40
84 Low Fuel Level Warn
(0-100)%
20
When the fuel level of the external sensor falls
below the set value, “Low Fuel Level” timer is
initiated. (this only concerns fuel level sensor
and does not concern low fuel level warning