HEM4300 Engine Controller User Manual Page 31 of 55
No.
Item
Range
Default
Description
engine will raise or drop speed.
5
Speed Control Upper Limit
(0-6000)r/min 2000
The max. speed of engine.
6
Idle Speed Control
(0-1)
1
0: Disable (After start idle delay is over,
engine enters normal running, engine
speed automatically raises to rated
speed);
1: Enable (After start idle delay is over,
engine enters normal running, engine
speed keeps idle value, you need to
manually raise speed).
7
Potentiometer
Speed Control
Enable
(0-1)
0
0: Disable; 1: Enable.
Start
Resist.
Value
(0-5000)Ω
50
Corresponding engine idle value.
Max.
Resist.
Value
(0-5000)Ω
950
Corresponding engine speed control
upper limit.
Sensor
Channel
(0-6)
0
0: Not Used;
1: Aux. Sensor 1;
2: Aux. Sensor 2;
3: Aux. Sensor 3;
4: Aux. Sensor 4;
5: Aux. Sensor 5;
6: Aux. Sensor 6.
8
Throttle
Speed Control
Enable
(0-1)
0
0: Disable; 1: Enable.
Start Volt
Value
(0-5.00)V
0.75
Corresponding engine idle value.
Max. Volt
Value
(0-5.00)V
3.84
Corresponding engine speed control
upper limit.
Sensor
Channel
(0-6)
0
0: Not Used;
1: Aux. Sensor 1;
2: Aux. Sensor 2;
3: Aux. Sensor 3;
4: Aux. Sensor 4;
5: Aux. Sensor 5;
6: Aux. Sensor 6.
9
Continuous Active for Key
Speed Control
(0-1)
0
0: Disable; 1: Enable.
Aux. Input Ports
Aux. Input 1
1
Contents Setting
(0-59)
4
Emergency stop input. Details see
Table 12.
2
Active Type
(0-1)
0
0: Close 1: Open
3
Active Electric Level
(0-1)
0
0: Low electric level; 1: High electric
Содержание HEM4300