HEM4300 Engine Controller User Manual Page 29 of 55
No.
Item
Range
Default
Description
choosing
custom
resist./voltage/current type curve.
Aux. Sensor 1~6 Setting
1
Sensor Type
(0-4)
0
0: Not Used
1: Temperature Sensor
2: Pressure Sensor
3: Level Sensor
4: Vibration Sensor
2
Curve Type
Changes according to sensor types;
3
Open Action
(0-2)
0
0: Warning 1: Shutdown 2: None
4
Display Unit
(0-1)
0
0: °C 1: °F
NOTE
: Unit is different for different sensor.
5
Over
Shutdown
Enable
(0-1)
0
When external sensor value is larger
than this value, controller issues
shutdown alarm; Alarm enable and
delay value can be set.
Set
(0-9000)
100
Delay
(0-3600)s
5
6
Under
Shutdown
Enable
(0-1)
0
When external sensor value is less
than this value, controller issues
shutdown alarm; alarm enable and
delay value can be set.
Set
(0-9000)
10
Delay
(0-3600)s
5
7
Over Warn
Enable
(0-1)
0
When external sensor value is larger
than this value, controller issues
warning alarm; alarm enable, return
and delay values can be set.
Set
(0-9000)
90
Return
(0-9000)
80
Delay
(0-3600)s
5
8
Under Warn
Enable
(0-1)
0
When external sensor value is less
than this value, controller issues
warning alarm; alarm enable, return
and delay values can be set.
Set
(0-9000)
20
Return
(0-9000)
30
Delay
(0-3600)s
5
9
Custom Curve
Corresponding curve needs to be set in
choosing
custom
resist./voltage/current type curve.
Sensor Correlation Setting
1
Temp. Correlation
(0-6)
0
0: ECU Coolant Temp;
1: Aux. Sensor 1;
2: Aux. Sensor 2;
3: Aux. Sensor 3;
4: Aux. Sensor 4;
5: Aux. Sensor 5;
6: Aux. Sensor 6.
2
Oil Pressure Correlation
(0-6)
0
0: ECU Oil Pressure;
1: Aux. Sensor 1;
2: Aux. Sensor 2;
3: Aux. Sensor 3;
4: Aux. Sensor 4;