HEM4300 Engine Controller User Manual Page 21 of 55
No.
Type
Description
14
OP Sensor Open
When controller detects sensor is open and action type is selected
“Shutdown”, it issues shutdown alarm signal.
15
Low OP Shut
When controller detects oil pressure is below pre-set shutdown
value, it issues shutdown alarm signal.
16
Aux. Sensor 1~6 Open
When controller detects sensor is open, and action type is selected
“Shutdown”, it issues shutdown alarm signal.
17
Aux. Sensor 1~6 High
When controller detects sensor value is above pre-set upper
shutdown limit value, it issues shutdown alarm signal.
18
Aux. Sensor 1~6 Low
When controller detects sensor value is below pre-set lower
shutdown limit value, it issues shutdown alarm signal.
19
Input 1~8 Shut
When digital input is configured to shutdown alarm, and if it is
active, it issues corresponding input shutdown alarm signal.
20
Maintenance 1~15 Shut
When maintenance countdown reaches set time or date and action
type is selected “Shutdown”, controller issues shutdown alarm
signal.
21
End of Mandate Time
When controller time reaches mandate time, and mandate time due
action is selected “Shutdown”, controller issues shutdown alarm
signal.