![Smartgen APC615 Скачать руководство пользователя страница 42](http://html.mh-extra.com/html/smartgen/apc615/apc615_user-manual_1297473042.webp)
APC615 Pump Unit Controller User Manual
APC615 Pump Unit Controller Version 1.0 2017-10-20 Page 42 of 54
10 COMMISSIONING
Please make sure the following checks are made before commissioning,
a) Ensure all the connections are correct and wires diameter is suitable.
b)
Ensure that the controller DC power has fuse, controller’s positive and negative connected to start
battery are correct.
c) Take proper action to prevent engine to crank success (e. g. Remove the connection wire of fuel
valve). If checking is OK, make the start battery power on; choose manual mode and controller will
executive routine.
d) Set controller under manual
mode, press “start” button, genset will start. After the cranking times as
setting, controller will send signal of start f
ailure; then press “Stop” to reset controller.
e) Recover the action to prevent engine to crank success (e. g. Connect wire of fuel valve), press start
button again, genset will start. If everything goes well, genset will normal running after idle running (if
idle run be set). During this time, please watch for engine’s running situations
f) If there is any other question, please contact Sm
artGen’s service.