![Smartgen APC615 Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/smartgen/apc615/apc615_user-manual_1297473013.webp)
APC615 Pump Unit Controller User Manual
APC615 Pump Unit Controller Version 1.0 2017-10-20 Page 13 of 54
Display
Description
Adjust speed type set as
2: CAN Adjust Speed;
adjust speed
stabilize object set as
1: Inlet Pressure;
display screen is showed as
left. In this screen, users can select adjust speed mode (manual or
auto) via pressing
and
keys. In manual mode, through
pressing
or
key to adjust percentage; in auto mode,
percentage is adjusted automatically, thus the speed can be
adjusted.
Adjust speed type set as
2: CAN Adjust Speed;
adjust speed
stabilize object set as
2: Engine Speed;
display screen is showed as
left. In this screen, users can select adjust speed mode (manual or
auto) via pressing
and
keys. In manual mode, through
pressing
or
key to adjust percentage; in auto mode,
percentage is adjusted automatically, thus the speed can be
adjusted.
Adjust speed type set as
1: Relay Adjust Speed;
adjust speed
stabilize object set as
3: Manual Adjust Speed;
display screen is
showed as left. In this screen, users can select adjust speed mode
(manual or auto) via pressing
and
keys. In manual mode,
through pressing
or
key to connect or disconnect
rise/drop speed relay; in auto mode, speed control doesn
’t work.
NOTE
:
If adjust speed object is inlet pressure, flexible sensor 1 need to be set as inlet pressure, and
curve type must be effective.
Manual Adjust Speed:
Select
“Adjust Speed Type” in “Adjust Speed” item and configure it as “3:
Manual Adjust Speed
”. In adjust speed screen, users can manually adjust speed via pressing
or
(maully rise/drop speed only works in manual adjust speed mode and generator is normal
running).
Auto Adjust Speed:
After setting
“Auto Adjust Speed Mode”, when generator is normal running,
controller will auto adjust speed based on the parameters that the user defined, and adjust the
user-defined regulation object(outlet pressure/ Inlet pressure/ Engine speed) to the target value and
keep it stable.
Auto adjust speed includes relay adjust speed and CAN ajust speed.
Relay adjust speed controls the actuating motor of engine through rise/drop speed function of
output port.
Adj Speed Mode: Manual
Speed 1500RPM 0.0%
Outlet Pressure 1000kPa
Target Pressure 10kPa
Adj Speed Mode: Manual
Speed 1500RPM 0.0%
Adj Speed Mode: Manual
Speed 1500RPM