7
DEFINITION AND RANGE OF PARAMETERS
7.1 PARAMETER CONTENTS AND RANGE
No.
Items
Parameter
Default
Description
Language
1
Language
(0-2)
0
0: Simplified Chinese; 1:English; 2:Other
Timers
1
Start Delay
(0-3600)s
1
Time from remote start signal is active to start
the pump unit.
2
Return Delay
(0-3600)s
1
Time from remote stop signal is deactivated to
stop the pump unit.
3
Preheat Delay
(0-3600)s
0
Time of pre-powering heat plug before starter
is powered up.
4
Pre-start Fuel Time
(0-3600)s
1
Fuel relay output time before starter power on.
5
Cranking Time
(3-60)s
8
Time of starter powers up.
(If diesel driven pump unit is enabled, this time
also can be cranking time of diesel driven
pump unit).
6
Crank Rest Time
(3-60)s
10
The waiting time before second power up
when engine starts fail.
(If diesel driven pump unit is enabled, this time
also can be crank rest time of diesel driven
pump unit).
7
Safety On Delay
(0-3600)s
10
Alarms for low oil pressure, high temperature,
under speed, under frequency/voltage, charge
fail are deactivated during
“Safety On Delay”.
8
Start Idle Time
(0-3600)s
0
Idle running time of the pump unit when
starting.
9
Warming Up Time
(0-3600)s
10
Warming time between the pump unit take load
and high speed running.
10
Cooling Time
(0-3600)s
10
Radiating time before stop the pump unit, after
it unloads.
11
Stop Idle Time
(0-3600)s
0
Idle running time when pump unit stop.
12
ETS Solenoid Hold
(0-3600)s
20
Stop electromagnet’s power on time when
pump unit is stopping.
(If diesel driven pump unit is enabled, this time
also can be stop output time of diesel driven
pump unit).
13
Wait for Stop Time
(0-3600)s
0
Time between ending of pump unit idle delay
and stopped when “ETS Solenoid Hold” is set
as 0;
Time between ending of ETS delay and
stopped completely
when “ETS Hold output
time” is not 0.
14
After Stop Time
(0-3600)s
0
Time between pump unit stopped and standby.
15
Fuel
Pre-supply (0-12)h
2
When unit is in standby status and the output