Note:
User should open the shell of controller to change the jumper plug if your pump unit fitted with 4~20mA
sensor.
Fig.3
– Jumper Plug Transition Diagram
Table 13
– Sensor Type Conversion
Sensor Name
Jumper hat
Reistor-type
(wire jumper)
Voltage-type
(wire jumper)
Current-type
(wire jumper)
Temp. Sensor
Corresponding to
J1
Jumper plug to J1's
No.1
and
No.2
terminals
/
Jumper plug to J1's
No.2
and
No.3
terminals
Fuel
Level
Sensor
Corresponding to
J2
Jumper plug to J2's
No.1
and
No.2
terminals
/
Jumper plug to J2's
No.2
and
No.3
terminals
Oil
Pressure
Sensor
Corresponding to
J3 and J7
Jumper plug to J3's
No.1
and
No.2
terminals
Jumper plug to
J7.
Jumper plug to J3's
No.2
and
No.3
terminals
Outlet Pressure
Sensor
Corresponding to
J4 and J8
Jumper plug to J4's
No.1
and
No.2
terminals
Jumper plug to
J8.
Jumper plug to J4's
No.2
and
No.3
terminals
Flexible Sensor 1
Corresponding to
J5 and J9
Jumper plug to J5's
No.1
and
No.2
terminals
Jumper plug to
J9.
Jumper plug to J5's
No.2
and
No.3
terminals
Flexible Sensor 2
Corresponding to
J6 and J10
Jumper plug to J6's
No.1
and
No.2
terminals
Jumper plug to
J10.
Jumper plug to J6's
No.2
and
No.3
terminals