Basic Functioning Theory
6.6
Foundation Fieldbus to 4-20mA Analog Conversion (HI302-O)
In a similar way, a board with analog output circuits is capable of controlling a current
used by actuators, for example. These circuits are protected against high voltage by zener
diodes, against overheating and against inverted polarity. The output module uses circuits
required by current control (UX), in addition to a (UXX) DA converter and a referential
4VO96 (U8) voltage source. These circuits make up 8 independent channels for current
control working in parallel to HART digital communication. This backup board is
connected via CN2 and allows for the module to control the current’s value by means of a
MAO (or AO) block, utilized on any control mesh. All circuits forming the analog
acquisition are isolated from the others by means of a DC-DC (U1) converter and (U3,
U4...) optical couplers. The output backup board informs if the current loop is open or not,
through the circuit formed by UX. The output update period is approximately each 100 ms.