Section 1
1.1
INSTALLATION
Network Wiring
Access the wiring block by removing the Electrical Connection Cover. This cover can be locked
closed by the cover locking screw; to release the cover, rotate the locking screw clockwise. (See
Figure 1.1).
Figure 1.1 - Housing Adjusting Screw and Cover Lock
NOTE
The covers should be closed by hand completely, until the O’Ring is tight. For more safety, do not
use tools in this operation.
Cable access to wiring connections is obtained by two outlets. Conduit threads should be sealed by
means of code-approved sealing methods. The unused outlet connection should be plugged
accordingly.
The wiring block has screws on which fork or ring-type terminals can be fastened. See Figure 1.2.
Figure 1.2 - Wiring Block
NOTE
Due to each device particularity, check the electric connection block in the specific equipment
manual. The LD302 was used above as example.
For convenience there are two ground terminals: one inside the cover and one external, located
close to the conduit entries. More details are described in Shield and Grounding item.
Avoid routing signal wiring close to power cables or switching equipment.