Section 3
3.1
LOCAL ADJUSTMENT SETTING
To configure the function blocks and communication in the Series 302 equipment use the
configuration system called Host. The heavier and difficult task is automated and the risk of
configuration error is reduced. In the case of the Smar SYSTEM302 (Smar), an automatic
guide directs the user to commission the device properly. In this system, the equipment
addressing is made with the same physical tag.
The steps described below are based on the Smar – Syscon system configurator 6.1 Version.
Importantly, these settings may vary with each manufacturer.
Creating Devices
On the
Fieldbus
window, right-click the fieldbus icon and click
New > Device
. The
New
Device
dialog box will open.
Select the
Device Manufacturer
from the list and the
Device
Type
provided by the selected
manufacturer.
Select the
Device Revision
, then select the
DD Revision
and the
CF Revision
, or check the
option
Follow the Latest DD/CF Revision
to apply the latest revision for the selected device.
NOTE
If the option
Follow the Latest DD/CF Revision
is selected,
Syscon
will update the device with
the latest revision of the
DD
and
CF
every time the configuration file is opened. To disable the
automatic update, right-click the device icon, click
Exchange
and unmark that option on the
Exchange
dialog box.
Figure 3.1 - Device Dialog Box
Type a related tag for the device. If you do not define the tag,
Device n
will be the default tag,
where
n
is a sequential number for devices.
At the
Advanced Options
tab, select the options to automatically create and configure blocks
and parameters, according to the
Capabilities File
:
Creation Based on Default Template:
creates the device based on the
Default
Template
file for the selected
Device Revision
, located in the corresponding
Device Support
folder.
Create Resource Block:
automatically creates the
Resource
Block
of the selected
device. You can set the initial value for the
Mode Block
parameter.
Create Transducer Blocks:
automatically creates the
Transducer
Blocks
of the selected
device. You can set the initial value for the
Mode Block
parameter.
Содержание FY302
Страница 1: ...датчики давления уровня положения и другие полевые устройства Foundation Fieldbus www esma rt ru ...
Страница 6: ...GENERAL Installation Operation and Maintenance Manual VI ...
Страница 26: ...Series 302 FIELDBUS FOUNDATION Installation Operation and Maintenance Manual 1 20 ...
Страница 52: ...Series 302 FIELDBUS FOUNDATION Installation Operation and Maintenance Manual 4 4 ...