Series 302 FIELDBUS FOUNDATION – Installation, Operation and Maintenance Manual
3.4
NOTE
When the Syscon is in on-line mode, the
Device Selection
dialog box displays the devices that
have not been instantiated in the project.
If the user selects
Unspecified
in the
Device Tag
list and apply this tag to the instrument, the
Syscon will automatically generate a new tag for the standard instrument, based on the
preferences settings.
When operating in the
Advanced User
mode, the tab
Advanced Options
will be available in
the
Device Attributes
dialog box. Type the new physical address for the device.
Figure 3.7 - Advanced Options
Enter the physical address in the Address field of the instrument.
The normal commissioning operation should use the options
Commission
and
Decommission
. Only for some engineering and test scenarios, with the
Syscon
in
Advanced
Mode
options, it is possible to delete the
Device Id
from the instrument without using the
decommissioning procedure.
Click
Clear
to delete the
Device Id
. This procedure do not replace the
Decommission
option,
it only disassociates the physical device from the instrument on the configuration.
Click
Ok
to apply the alterations and conclude.
Master Backup Device
To configure the device to operate as a
Master Backup
, a
Link Master
should be selected.
Right-click the device icon and click
Attributes
. Click the down arrow on the
BOF Class
box
and select the Link
Master
option.
Click
Ok
to conclude.
Содержание FY302
Страница 1: ...датчики давления уровня положения и другие полевые устройства Foundation Fieldbus www esma rt ru ...
Страница 6: ...GENERAL Installation Operation and Maintenance Manual VI ...
Страница 26: ...Series 302 FIELDBUS FOUNDATION Installation Operation and Maintenance Manual 1 20 ...
Страница 52: ...Series 302 FIELDBUS FOUNDATION Installation Operation and Maintenance Manual 4 4 ...