6. In the drop-down list
Source for system active power
select the measurement source used
at the grid-connection point. If you are using an Energy Meter as measurement source, make
sure that the serial number of the Energy Meter used as the measurement source is displayed
under
PV system communication > Measured values > Meter on Speedwire
in the field
Serial Number
. If the correct serial number is not displayed, enter the serial number of the
required Energy Meter in the field.
7. Select [
Save
].
8. If you are using one of the analog current inputs of the Cluster Controller as measurement
source, configure the characteristic curve of this analog current input. By this means, the
current signals measured at the analog current input are converted into the corresponding
percentages for active power feed-in:
• Select the parameter group
Device > Inputs/outputs > Analog input
.
• Select [
Edit
].
• Set the characteristic curve depending on the connected sensor (see manual from
manufacturer).
• Select [
Save
].
Making settings for active power limitation
Requirements:
☐ The configuration for the active power limitation must be agreed upon with the responsible
grid operator.
☐ The necessary parameter for the active power limitation must be set in the inverter (see
Procedure:
1. Log into the Cluster Controller as
Installer
.
2. In the system tree, select the Cluster Controller and select the menu
Grid management
services
in the device menu.
3. Make the general settings:
• Select the parameter group
General settings > System control
.
• Select [
Edit
].
• In the drop-down list
Operating mode
, select the entry
Closed-loop control
.
• If you are using digital or analog inputs, enter the desired time interval in the field
Time
interval for the output value
.
• If necessary, adjust the value for the total system power. By default, the nominal inverter
power available in the system is used as the value for total system power.
– In the drop-down list
Total system power
select the entry
User-defined
.
– In the field
User-defined total system power
, enter the desired value.
• Select [
Save
].
4. Select the parameter group
Active power
and select [
Edit
].
5. In the group
Basic settings > Signal source
activate the checkbox
Manual specification
.
6. Select the group
Settings for manual specification
.
13 Grid Management Services
SMA Solar Technology AG
User Manual
67
ClusterController-BA-en-15